7

8.  Rotate the hinged control panel assembly out.

ROTATE OUT THE

CONTROL PANEL

ASSEMBLY

Figure 7.  Rotate Out Control Panel Assembly

9. 

Thread the UVA Lampholder / PCO cartridge two posts 

through the UVA lamp connector’s two holes.

10. Fasten the lamp socket to the UVA Lampholder / PCO 

cartridge using the two-brass finger nuts located in the 

literature bag.

BRASS FINGER

NUTS

A

IRFLOW

INDICATOR

WING 

NUTS

Figure 8.  Brass Finger and Wing Nuts

I

nstallIng

 UVa l

amPholder

Use the following procedure to install the UVA Lampholder 

/ PCO cartridge.

1.  While  aligning,  slide  the  UVA  Lampholder  /  PCO 

cartridge into case rails and align with rear mounting 

bracket.

2. 

Secure the UVA Lampholder / PCO cartridge to the two 

frame screw posts using the provided wing nuts (2).

NOTE: 

There is an arrow on the front of the component 

indicating the correct way to install it.

3.  Connect  UVA  lamp  4-pin  male  connector  to  ballast 

female 4-pin connector.

BALLAST FOUR PIN 

FEMALE CONNECTOR

LAMPHOLDER

ASSEMBLY

(Y6622)

Figure 9.  Ballast 4-Pin Female Connector

4.  Rotate  hinged  control  panel  assembly  back  into  the 

cabinet. Make sure no wiring is being pinched.

I

nstallIng

 a

Ir

 f

Ilter

Use the following procedure to install the air filter.

1. 

Slide the Healthy Climate

®

 Carbon Clean 16

®

 Filter into 

the rails on the air inlet side of the cabinet. Verify proper 

airflow direction.

2.  Securely fasten the access panel.

3. 

Plug one end of the provided power cord into the 

receptacle on the cabinet and the other end into a power 

receptacle.

4. 

Look through the view port in the access panel to check 

that the UVA lamp is illuminated.

NOTE: 

On initial start-up, the UVA lamp may not reach full 

illumination for several minutes.

Содержание PureAir PCO3S-14-16

Страница 1: ...licensed professional HVAC installer or equivalent service agency or the gas supplier WARNING Electric shock hazard Can cause injury or death Disconnect all electrical power supplies before servicing...

Страница 2: ...ay be required to lower total volatile organic compounds to this level The Healthy Climate Carbon Clean 16 Filter combines industry leading MERV 16 filtration and carbon coated fiber matrix For full f...

Страница 3: ...Ballast Figure 1 Parts Identification Dimensions top for bottom 8 3 4 222 11 16 17 1 3 4 33 1 3 4 33 1 5 16 33 1 5 16 33 INLET AND OUTLET OPENING SAME SIZE A B C D 1 AIR FLOW Power Connection UVA Lamp...

Страница 4: ...t and the titanium dioxide PCO cartridge Packing material should be disposed of properly IMPORTANT Possible odor emissions Chemical reactions may cause temporary odors after initial start up or after...

Страница 5: ...5 ton Modified Return Air Opening RETURN DUCT SUPPLY DUCT DUCT TRANSIITON Field Furnished FURNACE OR AIR HANDLER PCO3S RETURN DUCT SUPPLY DUCT OPTIONAL RAB RETURN AIR BASE PCO3S RETURN DUCT SUPPLY DUC...

Страница 6: ...iate fasteners to secure cabinet to the return air side of the air handling unit 4 Use field provided sheet metal screws 1 25mm maximum length to fasten the return air duct to the other side of the ca...

Страница 7: ...d wing nuts 2 NOTE There is an arrow on the front of the component indicating the correct way to install it 3 Connect UVA lamp 4 pin male connector to ballast female 4 pin connector BALLAST FOUR PIN F...

Страница 8: ...tached to the C terminals Keep all communication wiring as far away from the house electrical wiring and large electrical appliances as possible Recommended minimal distance is 15 feet 5 meters Unused...

Страница 9: ...to indicate the reset was successful Control Manual Reset When pressing both the SW1 and SW2 switches at the same time for ten seconds will reset the control to factory default Control can also be re...

Страница 10: ...Advance equipment configurations notifications tests diagnostics installation reports and general information about the system Go to menu settings advanced settings view dealer control center dealer c...

Страница 11: ...date for filter Date last filter reset was accomplished This is for display purposes only and cannot be changed Purifier life Provides percentage of remaining purifier life This is for display purpos...

Страница 12: ...n of the alert code press the down arrow to expand the description Service Urgent alerts are displayed on Home user screen under the homeowner and installer alert buttons Service Urgent means that a s...

Страница 13: ...ltage wiring transformer and equipment Check for incorrectly wired or loose or spliced connections between system components devices or units Make sure all unused wires are tied together and taken bac...

Страница 14: ...he thermostat Check the wiring connections between components Ohm wires Cycle power Any component that is miss wired may cause a false component code to be shown on system component Disconnect all wir...

Страница 15: ...Service Soon PA UV Lamp Off The light is determined to be off when the last three last light intensities measurements are below the set threshold Light is determined on after 1 set of five samples ar...

Страница 16: ...holder PCO cartridge and UVA lamp require annual replacement More frequent filter replacement may be required in applications with heavier dust or dirt loads or if you notice a reduction in odor remov...

Страница 17: ...e out the hinged control panel 6 Disconnect UVA lamp electrical connector from ballast 7 Remove both fasteners securing the UVA Lampholder PCO cartridge from the chassis 8 Slide out the UVA Lampholder...

Страница 18: ...to the PCO cabinet NO Repair Issues Is the lamp on Check ballast voltages see table below on red and blue wires at 4 pin connector Replace any burned out or damaged components NO Is the lamp on NO Con...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: