Communicating Control Functions

UV Lamp Sensor Control 

Board  

Pushing and Holding the Change Filter buon or the Change Lamp buon for 5 seconds will reset the control 

Change Filter 

buon 

Lamp sensor control board 

ribbon connecon 

High side pressure tap 

Low side pressure 

tap 

Change Lamp 

buon 

iComfort wiring 

connecons 

PCO unit size 
selecon

 

jumper

 

Ch

bu

Filter Control Board 

Figure 13. PureAir 

S

 Communicating Control

Pco m

odel

 (h2) J

UmPers

A series of jumpers is used to select which size pure air the 

control is installed.

Jumper selections are: 

• 

Position 1 (pins 1 and 2 shorted): 14-16 (nominal airflow 

= 1400cfm)

• 

Position 2 (pins 2 and 3 shorted): 16-16 (nominal airflow 

= 1600cfm)

• 

Position 3 (pins 3 and 4 shorted): 20-16 (nominal airflow 

= 2000cfm)

NOTE: 

The correct size selection should already be set 

from the factory.

14-16

Jumper Setting

16-16

Jumper Setting

20-16

Jumper Setting

Jumper

Figure 14. Model Jumper Selection

c

hange

 l

amP

 r

eset

 (sW1)

After bulb replacement, press and hold for three seconds 

SW1 - Change Lamp button. This resets the system.
A LED will start to flash after three seconds to indicate the 

reset was successful.

c

hange

 f

Ilter

 r

eset

 (sW2)

After air filter replacement, press and hold for three seconds 

SW2 - Change Filter. This resets the system. 
A LED will start to flash after three seconds to indicate the 

reset was successful.

c

ontrol

 m

anUal

 r

eset

When  pressing  both  the  SW1  and  SW2  switches  at  the 

same time for ten seconds will reset the control to factory 

default.

Control can also be reset by using the S30 thermostat. Go 

to 

menu

 > 

settings

 > 

advanced settings

 > 

view dealer 

control center

 > 

equipment

 > 

reset

 > 

reset  HVAC 

equipment

.

Lennox S30 Thermostat Setup

s

ystem

 s

etUP

 (c

ommIssIonIng

)

During the initial or rerunning the commissioning of the 

system using the iComfort S30 Ultra Smart thermostat, the 

system will auto-detect the presence of the 

PureAir

 

S

 unit.

Follow the instructions provided with the thermostat for the 

system commissioning process. If the PureAir 

S

 component 

is successfully detected, it will appear on the found 

equipment screen.

NOTE: 

During commissioning the blower will turn on and 

run at three different CFM settings for the PCO 

filter calibration to take place. This may be well in 

advanced before the display is fully up and running. 

This is a normal process. The blower may run as 

long as 90 seconds at each CFM setting to complete 

the filter calibration .

equipment found

welcome to iComfort

previous

continue

system

+/-

Thermostat

104553-01

Heat Pump

XP25-060-230

PureAir

PCO3S16-16

Smart Hub

Air Handler

CBX40UHV-060; 1

non-communicating

equipment

Mag-Mount

1045498-01

Figure 15. Equipment Found

r

emInders

Default  setting  is  sensor-based.  Additional  options  are 

calendar time, run-time or disabled. On the reminder screen, 

select 

PureAir

 

maintenance to change the option.

Содержание PureAir PCO3S-14-16

Страница 1: ...licensed professional HVAC installer or equivalent service agency or the gas supplier WARNING Electric shock hazard Can cause injury or death Disconnect all electrical power supplies before servicing...

Страница 2: ...ay be required to lower total volatile organic compounds to this level The Healthy Climate Carbon Clean 16 Filter combines industry leading MERV 16 filtration and carbon coated fiber matrix For full f...

Страница 3: ...Ballast Figure 1 Parts Identification Dimensions top for bottom 8 3 4 222 11 16 17 1 3 4 33 1 3 4 33 1 5 16 33 1 5 16 33 INLET AND OUTLET OPENING SAME SIZE A B C D 1 AIR FLOW Power Connection UVA Lamp...

Страница 4: ...t and the titanium dioxide PCO cartridge Packing material should be disposed of properly IMPORTANT Possible odor emissions Chemical reactions may cause temporary odors after initial start up or after...

Страница 5: ...5 ton Modified Return Air Opening RETURN DUCT SUPPLY DUCT DUCT TRANSIITON Field Furnished FURNACE OR AIR HANDLER PCO3S RETURN DUCT SUPPLY DUCT OPTIONAL RAB RETURN AIR BASE PCO3S RETURN DUCT SUPPLY DUC...

Страница 6: ...iate fasteners to secure cabinet to the return air side of the air handling unit 4 Use field provided sheet metal screws 1 25mm maximum length to fasten the return air duct to the other side of the ca...

Страница 7: ...d wing nuts 2 NOTE There is an arrow on the front of the component indicating the correct way to install it 3 Connect UVA lamp 4 pin male connector to ballast female 4 pin connector BALLAST FOUR PIN F...

Страница 8: ...tached to the C terminals Keep all communication wiring as far away from the house electrical wiring and large electrical appliances as possible Recommended minimal distance is 15 feet 5 meters Unused...

Страница 9: ...to indicate the reset was successful Control Manual Reset When pressing both the SW1 and SW2 switches at the same time for ten seconds will reset the control to factory default Control can also be re...

Страница 10: ...Advance equipment configurations notifications tests diagnostics installation reports and general information about the system Go to menu settings advanced settings view dealer control center dealer c...

Страница 11: ...date for filter Date last filter reset was accomplished This is for display purposes only and cannot be changed Purifier life Provides percentage of remaining purifier life This is for display purpos...

Страница 12: ...n of the alert code press the down arrow to expand the description Service Urgent alerts are displayed on Home user screen under the homeowner and installer alert buttons Service Urgent means that a s...

Страница 13: ...ltage wiring transformer and equipment Check for incorrectly wired or loose or spliced connections between system components devices or units Make sure all unused wires are tied together and taken bac...

Страница 14: ...he thermostat Check the wiring connections between components Ohm wires Cycle power Any component that is miss wired may cause a false component code to be shown on system component Disconnect all wir...

Страница 15: ...Service Soon PA UV Lamp Off The light is determined to be off when the last three last light intensities measurements are below the set threshold Light is determined on after 1 set of five samples ar...

Страница 16: ...holder PCO cartridge and UVA lamp require annual replacement More frequent filter replacement may be required in applications with heavier dust or dirt loads or if you notice a reduction in odor remov...

Страница 17: ...e out the hinged control panel 6 Disconnect UVA lamp electrical connector from ballast 7 Remove both fasteners securing the UVA Lampholder PCO cartridge from the chassis 8 Slide out the UVA Lampholder...

Страница 18: ...to the PCO cabinet NO Repair Issues Is the lamp on Check ballast voltages see table below on red and blue wires at 4 pin connector Replace any burned out or damaged components NO Is the lamp on NO Con...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: