6

Installation

U

nIqUe

 f

Ield

-s

UPPlIed

 I

nstallatIon

 I

tems

The following items are recommended to have on-hand for 

installation of the unit.

• 

Cotton gloves and cloth (to remove finger prints from 

UVA lamp)

• 

Aluminum foil tape or water-based mastic (NOT 

sili

-

cone) to be applied as a sealant.

s

electIng

 l

ocatIon

The unit must be installed in the return air duct upstream of 

the supply blower. Allow a 30” (76cm) service clearance in 

front of the access panel as shown in figure 4. The air filter 

and UVA Lampholder / PCO cartridge must be removable.

Allow Approximately

30” (76cm) of Clearance

Figure 4. 

Service Clearance

I

nstallIng

 c

abInet

The cabinet may either be installed on a level installation 

deck or platform adjacent to the air handler or it may be 

suspended from the rafters using metal strapping. If straps 

are used, take care when attaching straps to the cabinet. 

Ensure fasteners do not interfere with internal components 

of  the  cabinet.  The  air  filter  and  UVA  Lampholder  /  PCO 

cartridge must be able to slide freely into the cabinet.

1.  Locate and remove the UVA Lampholder / PCO cartridge 

from the cabinet.

NOTE: 

Oil on metal surfaces may cause odors. Use mild 

soap and water solution to wash all new duct and 

transition surfaces.

2. 

Use the air flow directional label on the inside of the UVA 

Lampholder / PCO cartridge to orient the unit. 

3.  Properly  position  the  cabinet  next  to  the  return  air 

opening of the air handling unit. Use sheet metal screws 

1” (25mm) maximum length, rivets or other appropriate 

fasteners to secure cabinet to the return air side of the 

air handling unit.

4.  Use  field-provided  sheet  metal  screws  1”  (25mm) 

maximum length to fasten the return air duct to the other 

side of the cabinet. Attachment holes are provided in 

housing.

5.  Use  field-provided  aluminum  foil  tape  or  water-based 

mastic to seal all joints between the cabinet, air handler 

and duct.

6.  In  high  humidity  applications,  wrap  cabinet  with  field-

provided  2”  (50mm)  foil-faced  insulation  (foil  on  the 

outside) to prevent condensation.

I

nstallIng

 UVa l

amP

Use cotton gloves or a cotton cloth to protect the lamp and 

your hands during unpacking and installation.

1.  Remove cabinet access panel.

2. 

The  UVA  Lampholder  /  PCO  cartridge  is  shipped  in  a 

protective packaging. Packaging must be removed 

prior to installation. Take care to prevent damage while 

removing from packaging.

3.  Locate the UVA lamp box, which is taped to the inside of 

cabinet and carefully remove. Set UVA lamp box aside 

while preparing cabinet for UVA lamp installation.

4.  Remove (slide out) Healthy Climate

®

 Carbon Clean 16

®

 

Filter from cabinet.

5. 

Disconnect the lampholder cable assembly from the 

UVA lamp ballast connector.

6.  Carefully remove lamp from UVA lamp box and secure 

the UVA lamp electrical connector to the UVA lamp by 

sliding the UVA lamp pins into the slot. Proper connection 

will make a snapping sound.

DEPRESS RED BUTTON

ONLY TO RELEASE UVA

LAMP FROM SOCKET.

Figure 5.  Releasing UVA Lamp from Socket

7. 

Slide  the  UVA  lamp  into  UVA  Lampholder  /  PCO 

cartridge. Verify that the UVA lamp is secure to the one 

metal  UVA  lamp  clamp  located  mid-way  on  the  UVA 

lamp reflector.

METAL UVA LAMP

CLAMP

UVA LAMP REFLECTOR

Figure 6.  UVA Lamp Metal Clamp

Содержание PureAir PCO3S-14-16

Страница 1: ...licensed professional HVAC installer or equivalent service agency or the gas supplier WARNING Electric shock hazard Can cause injury or death Disconnect all electrical power supplies before servicing...

Страница 2: ...ay be required to lower total volatile organic compounds to this level The Healthy Climate Carbon Clean 16 Filter combines industry leading MERV 16 filtration and carbon coated fiber matrix For full f...

Страница 3: ...Ballast Figure 1 Parts Identification Dimensions top for bottom 8 3 4 222 11 16 17 1 3 4 33 1 3 4 33 1 5 16 33 1 5 16 33 INLET AND OUTLET OPENING SAME SIZE A B C D 1 AIR FLOW Power Connection UVA Lamp...

Страница 4: ...t and the titanium dioxide PCO cartridge Packing material should be disposed of properly IMPORTANT Possible odor emissions Chemical reactions may cause temporary odors after initial start up or after...

Страница 5: ...5 ton Modified Return Air Opening RETURN DUCT SUPPLY DUCT DUCT TRANSIITON Field Furnished FURNACE OR AIR HANDLER PCO3S RETURN DUCT SUPPLY DUCT OPTIONAL RAB RETURN AIR BASE PCO3S RETURN DUCT SUPPLY DUC...

Страница 6: ...iate fasteners to secure cabinet to the return air side of the air handling unit 4 Use field provided sheet metal screws 1 25mm maximum length to fasten the return air duct to the other side of the ca...

Страница 7: ...d wing nuts 2 NOTE There is an arrow on the front of the component indicating the correct way to install it 3 Connect UVA lamp 4 pin male connector to ballast female 4 pin connector BALLAST FOUR PIN F...

Страница 8: ...tached to the C terminals Keep all communication wiring as far away from the house electrical wiring and large electrical appliances as possible Recommended minimal distance is 15 feet 5 meters Unused...

Страница 9: ...to indicate the reset was successful Control Manual Reset When pressing both the SW1 and SW2 switches at the same time for ten seconds will reset the control to factory default Control can also be re...

Страница 10: ...Advance equipment configurations notifications tests diagnostics installation reports and general information about the system Go to menu settings advanced settings view dealer control center dealer c...

Страница 11: ...date for filter Date last filter reset was accomplished This is for display purposes only and cannot be changed Purifier life Provides percentage of remaining purifier life This is for display purpos...

Страница 12: ...n of the alert code press the down arrow to expand the description Service Urgent alerts are displayed on Home user screen under the homeowner and installer alert buttons Service Urgent means that a s...

Страница 13: ...ltage wiring transformer and equipment Check for incorrectly wired or loose or spliced connections between system components devices or units Make sure all unused wires are tied together and taken bac...

Страница 14: ...he thermostat Check the wiring connections between components Ohm wires Cycle power Any component that is miss wired may cause a false component code to be shown on system component Disconnect all wir...

Страница 15: ...Service Soon PA UV Lamp Off The light is determined to be off when the last three last light intensities measurements are below the set threshold Light is determined on after 1 set of five samples ar...

Страница 16: ...holder PCO cartridge and UVA lamp require annual replacement More frequent filter replacement may be required in applications with heavier dust or dirt loads or if you notice a reduction in odor remov...

Страница 17: ...e out the hinged control panel 6 Disconnect UVA lamp electrical connector from ballast 7 Remove both fasteners securing the UVA Lampholder PCO cartridge from the chassis 8 Slide out the UVA Lampholder...

Страница 18: ...to the PCO cabinet NO Repair Issues Is the lamp on Check ballast voltages see table below on red and blue wires at 4 pin connector Replace any burned out or damaged components NO Is the lamp on NO Con...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: