Table 6. 

Alert Codes and Troubleshooting

GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, 

ZA=Zone system and TS=Thermostat

Alert 

Code

Priority 

Condition

Actual Displayed 

Alert Text 

Under dealer 

control center > 

Notifications

Component or System Operational State 

and Troubleshooting Tip

How to clear alert code

120

Service Soon

Unresponsive 

Device

There is a delay in the system component responding to the 

system. Typically this alert code does not cause any operational 

issues and will clear on its own. 
•  This alert code is usually caused by a delay in the outdoor unit 

responding to the thermostat.

•  Leaking voltage from strands within the bundle.

 

> Land only the

 R

 wire on the 

R

 terminal to load the bundle with 

24VAC.

 

Typically only the 

R

 wire needs to be landed to identify if 

voltage is leaking.

 

If voltage is present checking the other wires is informational 

only but not needed.

 

If voltage is not present checking the other wires one at a 

time would be needed.

 

> Check each loose wire in AC mode to 

C

 on circuit board.

 

► Good voltage is .03 -.3VAC leaking voltage is not the issue.

 

Acceptable can be up to .7VAC with moderate success.

 

► Some units have worked with up to 1.2VAC with occasional 

success.

 

► Voltage over 1.2VAC needs to be addressed. 

Automatically clears after an 

unresponsive system component 

(device) responds to any inquiry.

124

Service 

Urgent

Tstat Lost 

Communication 

To Smarthub

The thermostat has lost communication with a system component 

for more than three minutes. System component has lost 

communication with the thermostat. 
•  Check the wiring connections between components.

• 

Ohm wires.

•  Cycle power. 

• 

Any component that is miss-wired may cause a false component 

code to be shown on system component. 

•  Disconnect all wiring to other system components and check 

communication one at a time. 

NOTE: 

When  using  a  float  switch,  use  isolation  relay  to  break 

common wire to outdoor unit. For testing purposes, re-

move float switch from the circuit

This alert code stops all associated system operations and waits 

for a heartbeat message from the system component that is not 

communicating. 

Automatically clears after 

communication is re-established 

with applicable system component 

(device).

125

Service 

Urgent

Control 

Hardware 

Problem

There is a hardware problem on a system component control. 

There is a control hardware problem. 
•  In system using iHarmony zoning, the system will remain in 

non-zone mode (all dampers open) for five minutes after priority 

condition no longer exist.

• 

In systems using a Equipment Interface Module, remove jumper 

if present on indoor unit between 

R

 and 

W2

.

•  In systems using a PureAir 

S

, the pure air control board jumper 

selector is missing.

If none of the above tips are applicable, then replace the control if 

the problem prevents operation and is persistent. 

Automatically clears five minutes 

after the issue no longer exists.

126

Service 

Urgent

Control Internal 

Communication 

Prob

There is an internal hardware problem on the system component 

control. In addition, if you have zoning the alert code is triggered 

when your zone temperature is deviating away from set point 

persistently.
•  Typically the system component control will reset itself. 

• 

Replace  the  system  component  (device)  control  if  the  problem 

prevents operation and is persistent. 

Automatically clears 300 seconds 

after the issue no longer exists.

Содержание PureAir PCO3S-14-16

Страница 1: ...licensed professional HVAC installer or equivalent service agency or the gas supplier WARNING Electric shock hazard Can cause injury or death Disconnect all electrical power supplies before servicing...

Страница 2: ...ay be required to lower total volatile organic compounds to this level The Healthy Climate Carbon Clean 16 Filter combines industry leading MERV 16 filtration and carbon coated fiber matrix For full f...

Страница 3: ...Ballast Figure 1 Parts Identification Dimensions top for bottom 8 3 4 222 11 16 17 1 3 4 33 1 3 4 33 1 5 16 33 1 5 16 33 INLET AND OUTLET OPENING SAME SIZE A B C D 1 AIR FLOW Power Connection UVA Lamp...

Страница 4: ...t and the titanium dioxide PCO cartridge Packing material should be disposed of properly IMPORTANT Possible odor emissions Chemical reactions may cause temporary odors after initial start up or after...

Страница 5: ...5 ton Modified Return Air Opening RETURN DUCT SUPPLY DUCT DUCT TRANSIITON Field Furnished FURNACE OR AIR HANDLER PCO3S RETURN DUCT SUPPLY DUCT OPTIONAL RAB RETURN AIR BASE PCO3S RETURN DUCT SUPPLY DUC...

Страница 6: ...iate fasteners to secure cabinet to the return air side of the air handling unit 4 Use field provided sheet metal screws 1 25mm maximum length to fasten the return air duct to the other side of the ca...

Страница 7: ...d wing nuts 2 NOTE There is an arrow on the front of the component indicating the correct way to install it 3 Connect UVA lamp 4 pin male connector to ballast female 4 pin connector BALLAST FOUR PIN F...

Страница 8: ...tached to the C terminals Keep all communication wiring as far away from the house electrical wiring and large electrical appliances as possible Recommended minimal distance is 15 feet 5 meters Unused...

Страница 9: ...to indicate the reset was successful Control Manual Reset When pressing both the SW1 and SW2 switches at the same time for ten seconds will reset the control to factory default Control can also be re...

Страница 10: ...Advance equipment configurations notifications tests diagnostics installation reports and general information about the system Go to menu settings advanced settings view dealer control center dealer c...

Страница 11: ...date for filter Date last filter reset was accomplished This is for display purposes only and cannot be changed Purifier life Provides percentage of remaining purifier life This is for display purpos...

Страница 12: ...n of the alert code press the down arrow to expand the description Service Urgent alerts are displayed on Home user screen under the homeowner and installer alert buttons Service Urgent means that a s...

Страница 13: ...ltage wiring transformer and equipment Check for incorrectly wired or loose or spliced connections between system components devices or units Make sure all unused wires are tied together and taken bac...

Страница 14: ...he thermostat Check the wiring connections between components Ohm wires Cycle power Any component that is miss wired may cause a false component code to be shown on system component Disconnect all wir...

Страница 15: ...Service Soon PA UV Lamp Off The light is determined to be off when the last three last light intensities measurements are below the set threshold Light is determined on after 1 set of five samples ar...

Страница 16: ...holder PCO cartridge and UVA lamp require annual replacement More frequent filter replacement may be required in applications with heavier dust or dirt loads or if you notice a reduction in odor remov...

Страница 17: ...e out the hinged control panel 6 Disconnect UVA lamp electrical connector from ballast 7 Remove both fasteners securing the UVA Lampholder PCO cartridge from the chassis 8 Slide out the UVA Lampholder...

Страница 18: ...to the PCO cabinet NO Repair Issues Is the lamp on Check ballast voltages see table below on red and blue wires at 4 pin connector Replace any burned out or damaged components NO Is the lamp on NO Con...