4
s
PecIfIcatIons
Table 2.
Specifications
Model
Weight
(lbs.)
Electrical
Power
Consumption
Operating
Environment
Pleated Filter
Efficiency
Listings
PCO3S-14-16
24
120V, 50/60 Hz, 0.48 Amps
-- Maximum
or
230 V, 50/60 Hz, 0.24 Amps
-- Maximum
120VAC and
230VAC - 58
Watts Nominal
0°F to 140°F outside
of duct
10 to 60 percent relative
humidity
(Optimal performance
at 50 percent relative
humidity)
Minimum
Efficiency
Rating Value
(MERV) 16
ETL safety listing
report 3061144A.
Conforms to UL
STD 1598
Certified to CSA
STD C22.2 no.
250.0.
PCO3S-16-16
27
PCO3S-20-16
27
Table 3.
Approximate Air Flow Resistance
(Cabinet and Filter)
Capacity
(Tons)
Flow Rate
(CFM)
Pressure Drop (in. w.g.)
PCO3S-14-16
PCO3S-16-16
PCO3S-20-16
Low /
Variable
400
0.05
0.04
0.03
Low /
Variable
600
0.07
0.07
0.06
2
800
0.11
0.11
0.08
2.5
1000
0.15
0.15
0.11
3
1200
0.20
0.20
0.15
3.5
1400
0.25
0.25
0.18
4
1600
*
0.31
0.22
4.5
1800
*
*
0.27
5
2000
*
*
0.31
*Not recommended. Excessive system pressure drop can damage
HVAC system and reduce performance.
IMPORTANT
Do not wash UVA Lampholder / PCO cartridge. Soap
and water will destroy the titanium dioxide catalyst that
coats the cartridge surface.
IMPORTANT
Unpacking required.
Remove all protective packing material from the UVA
lamp (taped to the cabinet) and the titanium dioxide
PCO cartridge.
Packing material should be disposed of properly.
IMPORTANT
Possible odor emissions. Chemical reactions may
cause temporary odors after initial start-up or after lamp
replacement. Odor may also be present after paint,
cleaning solutions or hobby materials have been used in
the conditioned space.
Some occupants may experience irritation or discomfort
during this period. If the irritation or discomfort lasts
longer than 48 hours, the homeowner should be advised
to contact a Lennox dealer.
IMPORTANT
The cabinet should be installed so that the UVA lamp will
be in the horizontal position.
IMPORTANT
This system is NOT intended to be used for removal of
active mold growth or continuous sources of high levels
of chemicals in the air.
For existing mold growth, the mold must be properly
removed PRIOR to installation of the PureAir
S
air
purification system.
IMPORTANT
This appliance is intended for return air duct installation
only.
Improper installation may damage PureAir
S
air
purification system, HVAC system, or other equipment
and may also void warranty.
CAUTION
UVA Lamp contains mercury.
Ingestion of or contact with mercury or mercury vapor is
hazardous to your health.
Take care when handling UVA lamp. If UVA lamp is
broken, avoid contact with mercury.
IMPORTANT
Healthy Climate
®
Carbon Clean 16
®
Filter cannot tolerate
direct exposure to UVA light.
Filter is protected by PCO cartridge shield.