21
Table 5. Advanced Settings
MENU
SETTING (default is bold)
Notes:
VCM = ASHRAE and
Ventilation Outdoor Condition
Override is set to ENABLED
Fresh Air Damper Ventilation CFM
Default is 75 CFM. Range is 20 to
250 CFM
STAGE 2 HP LOCK TEMP
Off
, 40°F, 45°F, 50°F, 55°F
Heat Pump - for dual-fuel applications (locks
out 2nd stage compressor)
COMPRESSOR PROTECT
On
or Off
This feature prevents the compressor from
being short cycled any time the compressor is
turned “OFF”.
DISPLAY PERFORMANCE REPORT
On
or Off
TERMINAL SETTINGS
H/D
Off
Humidify
Dehumidify
ACC
Off
Humidify
Dehumidify
Ventilation
O/B
O (energized during cooling)
B (energized during heating)
SYSTEM TEST MODE
Confirm Button
Installer run tests to check all output relays.
Tests confirm signals between thermostat/unit
are being sent/received. Stops system to run
system tests
RESET SETTING
Confirm Button
Resets all parameters to factory settings
RESTART
Confirm Button
Reboot the thermostat.