40
Save Energy Default
Energy saving recommended set points for heating
and cooling can help save energy. The time and
temperatures reference in the following table are
pre-programmed into the thermostat to achieve
energy savings.
Scroll to
ENERGY SAVING DEFAULT
; touch to
select. Read the message on the screen and to
continue, touch
CONFIRM
.
Table 9. Energy Saving Set Points
Time
Heating
Cooling
Wake
70°F (21°C)
78°F (25°C)
Leave
62°F (17°C)
85°F (29°C)
Return
70°F (21°C)
78°F (25°C)
Sleep
62°F (17°C)
82°F (28°C)
NOTE:
Humidification and dehumidification are not part of the
energy savings program. A higher utility bill may occur
when not using the setpoints in this table.
Dehumidification Control
Normal and Max
Dehumidification options are listed at
menu
>
settings
>
humidity
. Under
Humidity Control,
select
dehumidify
to enable dehumidification. By
default it is
disabled
.
There are four setting options which are Normal,
Max, Humiditrol* and Aux Dehumidifier (requires
hardware accessory installed). Slide bar adjust with
a range of 40% to 60% RH.
Table 10.
Dehumidification Modes
Option
Description
Normal
• Activate: If RH measured is >= (RH set point + 2%),
and, Cool is ON, then D is inactive (open circuit),
and G is ON (if not already ON), and Y2 (if available)
is ON.
• Deactivate: If RH measured is <= (RH set point
- 2%) or Cool is OFF, then D is active (24VAC
present). G returns to the state determined by the
thermostat control, either ON, Auto, or CIRC. (OR)
If there is no more cool demand, then D is active
(24VAC present). G returns to the state determined
by the thermostat control, either ON, Auto, or CIRC,
and Y2 (if available) is OFF.
NOTE:
Note that H is inactive (open circuit) during
dehumidification.