20
Table 5. Advanced Settings
MENU
SETTING (default is bold)
Notes:
VENTILATION SETTINGS
Ventilator Type:
Fresh Air Damper
VENTILATION CONTROL MODE (VCM): ASHRAE or Timed
VCM = TIMED
Relay Setting to Work Fresh Air Damper
Closed or Open. Default is Closed.
Ventilation Minutes Per Hour
Default is 20 minutes. Range is 0 to 60 minutes
Ventilation High Outdoor Temperature Limit
Default is 100
⁰F. Range is 60⁰F to 115⁰F.
Ventilation Low Outdoor Temperature Limit
Default is 0
⁰
F. Range is -20
⁰
F to 55
⁰F.
Ventilation High Outdoor Dew Point Limit
Default is 55
⁰F. Range is 45⁰F to 80⁰F.
VCM = ASHRAE and
Ventilation Outdoor Condition
Override is set to DISABLED.
Relay Setting to Work Fresh Air Damper
Closed or Open. Default is Closed.
ASHRAE Compliance Check
YES or No: Current settings comply with
ASHRAE 62.2.
ASHRAE Infiltration Credit
Default is 0 CFM. Range is 0 to 200 CFM.
ASHRAE house floor area serviced by this
ventilator
Default is 2500 square feet. Range is 500 to
5000 square feet.
ASHRAE Number of Bedrooms
Default is 3. Range is 1 to 10.
Fresh Air Damper Ventilation CFM
Default is 75 CFM. Range is 20 to 250 CFM.
VCM = ASHRAE and
Ventilation Outdoor Condition
Override is set to ENABLED.
Ventilation High Outdoor Temperature Limit
Default is 100
⁰F. Range is 60⁰F to 115⁰F.
Ventilation Low Outdoor Temperature Limit
Default is 0
⁰
F. Range is -20
⁰
F to 55
⁰F.
Ventilation High Outdoor Dew Point Limit
Default is 55
⁰F. Range is 45⁰F to 80⁰F.
ASHRAE Compliance Check
YES or No: Current settings comply with
ASHRAE 62.2.
ASHRAE Infiltration Credit
Default is 0 CFM. Range is 0 to 200 CFM.
ASHRAE house floor area serviced by this
ventilator
Default is 2500 square feet. Range is 500 to
5000 square feet.
ASHRAE Number of Bedrooms
Default is 3. Range is 1 to 10.