Table 10. Alert Codes and Troubleshooting

Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the
Installer alert button. Minor and Moderate alerts are found only in the Installer alert button.

Alert

Code

Steps to clear

Alert Text

Priority

424

Moderate

The  liquid  line  temperature  sensor  has
malfunctioned.

In normal operation after outdoor control recognizes sensors, the alarm will be sent if valid
temperature reading is lost. Compare liquid line sensor resistance to temperature/resistance
charts in unit installation instructions. Replace sensor pack if necessary. At the beginning of
(any) configuration, furnace or airhandler control will detect the presence of the sensor(s). If
detected (reading in range), appropriate feature will be set as 'installed' and shown in the
iComfort WiFi

®

 thermostat 'About' screen. The alarm / fault will clear upon configuration, or

sensing normal values.

425

Minor

Outdoor  control  has  increased  minimum
compressor  speed  to  allow  for  proper  oil
return due to low ambient temperature.

Outdoor ambient temperature is below system limit. Control will attempt to run at lowest al
lowed compressor speed to allow for proper oil return. Automatically clears when outdoor am
bient temperature rises above limit for more then 5 minutes.

426

Critical

Excessive inverter alarms

After ten faults within one hour control will lockout. To clear disconnect power to outdoor unit
and restart. Inverter alarms 12 to 14 and 53 do not count towards this lockout condition.

427

Moderate  /
Critical

The  inverter  has  detected  a  DC  peak  fault
condition

.

If condition (55A or higher) is detected, outdoor unit will stop (compressor and fan). Anti-short
cycle is initiated. If peak current (55A or higher) occurs 10 times within an hour, system will
lockout. To clear, disconnect power to outdoor unit and restart.

428

Moderate  /
Critical

The inverter has detected a high main input
current condition

.

If condition is detected, outdoor unit will stop (compressor and fan). Anti-short cycle is initi
ated. If condition occurs 10 times within an hour, system will lockout. To clear, disconnect
power to outdoor unit and restart.

429

Moderate  /
Critical

The  inverter  has  detected  a  DC  link  low
voltage condition

.

Error occurs when DC link voltage drops below 14VDC. If condition is detected, outdoor unit
will stop (compressor and fan). Anti-short cycle is initiated. If condition occurs 10 times within
an hour, system will lockout. To clear, disconnect power to outdoor unit and restart.

430

Moderate  /
Critical

Compressor start-up failure

If condition is detected, outdoor unit will stop (compressor and fan). Anti-short cycle is initi
ated. If condition occurs 10 times within an hour, system will lockout. To clear, disconnect
power to outdoor unit and restart.

431

Moderate  /
Critical

The  inverter  has  detected  a  PFC  circuit
over-current condition

.

Error occurs when PFC detects a over current condition of 100A peak. If condition is detected,
outdoor unit will stop (compressor and fan). Anti-short cycle is initiated. If condition occurs 10
times within an hour, system will lockout. To clear, disconnect power to outdoor unit and re
start.

432

Moderate  /
Critical

The  inverter  has  detected  a  DC  link  high
voltage condition.

Error occurs when the DC link capacitor voltage is greater than 480VDC. If condition is detec
ted, outdoor unit will stop (compressor and fan). Anti-short cycle is initiated. If condition occurs
10 times within an hour, system will lockout. System will stop. To clear, disconnect power to
outdoor unit and restart.

433

Moderate  /
Critical

Compressor phase current is too high.

Error occurs when compressor peak phase current is greater than 28A. Inverter will issue
code 14 first and slow down to try to reduce the current.  If the current remains high, outdoor
unit will stop (compressor and fan). Antishort cycle is initiated. If condition occurs 5 times
within an hour, system will lockout. To clear disconnect power to outdoor unit and restart.

434

Moderate  /
Critical

Outdoor  control  has  lost  communications
with the inverter for greater than 3 minutes.

This error will occur when communication checksum error occurs for 3 minutes. Outdoor con
trol will stop all compressor demands, recycle power to the inverter by deenergizing the con
tactor for 2 minutes.

435

Moderate  /
Critical

Inverter internal error.

When this error occurs, the outdoor control will cycle power to the inverter by opening the con
tactor for 2 minutes. Outdoor

 control will cycle power to the inverter 3 times and then outdoor

unit is locked out

.

436

Moderate  /
Critical

Inverter  heat  sink  temperature  exceeded
limit

.

This occurs when the heat sink temperature exceeds the inverter limit. Inverter will issue code
13 first and slow down to try to cool the heat since. If temperature remains high, outdoor unit
will stop (compressor and fan). Antishort cycle is initiated. If condition occurs 5 times within
an hour, system will lockout. System will stop. To clear, disconnect power to outdoor unit and
restart.

437

Moderate  /
Critical

Heat  sink  temperature  sensor  fault  has
occurred  (temperature  less  than  4  ºF  or
greater  than  264ºF  after  10  minutes  of
operation)

.

This occurs when the temperature sensor detects a temperature less than 0.4ºF or greater
than 264ºF after 10 minutes of operation. If condition is detected, outdoor unit will stop (com
pressor and fan). Antishort cycle is initiated. If condition occurs 5 times within an hour, system
will lockout. To clear disconnect power to outdoor unit and restart.

438

Moderate  /
Critical

The  inverter  has  detected  a  PFC  circuit
over-current condition

.

Error occurs when PFC detects an input over current condition of 35A peak. If condition is
detected, outdoor unit will stop (compressor and fan). Anti-short cycle is initiated. If condition
occurs 10 times within an hour, system will lockout. To clear, disconnect power to outdoor unit
and restart.

439

Moderate

Compressor  slowdown  due  to  high  input
current.

Input current is approaching a high limit. Compressor speed will automatically slow down. The
control continues sending the inverter speed demanded by the thermostat. The control will set
indoor CFM and outdoor RPM to values according to demand percentage rather than the actu
al Hz. Alarm is automatically clear.

440

Moderate

Compressor slowdown due to high heatsink
temperature.

Heat sink temperature is approaching limit. The compressor speed will automatically slow
down to reduce heatsink temperature. The control will set indoor CFM and outdoor RPM to
values according to demand percentage rather than the actual Hz. Alarm is automatically
cleared.

441

Moderate

Compressor 

slowdown 

due 

to 

high

compressor current.

Compressor current is approaching high limit. The compressor speed will automatically slow
down. The control will set indoor CFM and outdoor RPM to values according to demand per
centage rather than the actual Hz. Alarm is automatically cleared.

table continued on next page

Содержание iComfort CBX32MV-06

Страница 1: ... or Auxiliary Dehumidifier 5 Adjusting Equipment Parameters 6 Adjusting Humidification and De humidification Settings with Non Communicating Outdoor Units 11 Adjusting Humidification and De humidification Settings with Communicating Outdoor Units 13 Adjusting Zoning Control Settings 15 Using the Tests Diagnostics Features 17 Connecting to a Home Wi Fi Network 18 Registering the Thermostat 19 Accou...

Страница 2: ...oling humidification and De humidification without user involvement OUTDOOR TEMPERATURE SENSOR All Lennox branded communicating outdoor units contain a built in outdoor temperature sensor INSTALLATION AND SETUP COMMUNICATION ERROR SCREEN During initial thermostat start up if the following screen appears see figure 1 this will indicate that the thermostat has been incorrectly wired or has shorted w...

Страница 3: ...tatus remotely or receive email alerts when there is a problem no yes WARNING The dealer number is your Lennox account number Enter the entire dealer number including the letters and numbers e A12345 If you do not know your dealer number please contact your Lennox representative Are you sure you want to proceed Figure 5 Dealer Number Warning The following table lists all of the installer configura...

Страница 4: ...ot icomfort enabled you must be at the Add or Remove Non communicating equipment screen 1 Press the yes button on this screen see 1 2 In the non communicating device list screen use the arrows 2a to highlight Outdoor Unit Type and press edit 2b 3 Touch one of the radio buttons 3a to select a 1 or 2 Stage AC Unit or a 1 or 2 Stage HP Unit press save 3b 4 Use arrows 4a to highlight any red colored t...

Страница 5: ...icating equipment 4a 4b System Heat Pump Furnace Thermostat Bypass 24VAC Humidifier 5b 3a Figure 7 Add Non Communicating Device Humidifier ADDING HUMIDITROL OR AN AUXILIARY DEHUMIDIFIER Before adding a dehumidifier be sure that the dehumidifier is wired to the furnace or air handler control as shown on the Optional Accessories wiring diagram see page 37 the entire system is wired powered up and th...

Страница 6: ...ing highlight it then press Edit System 9 39 am Aug 15 2012 edit next back about resetAll Parameter Name Default Parameter Value Setting Increment Equipment Name keyboard input screen Filter 1 Timer Selection Calendar Time Calendar Time Run Time Filter 2 Timer Selection Calendar Time Calendar Time Run Time UV Bulb Timer Selection Calendar Time Calendar Time Run Time Humidifier Pad Timer Selection ...

Страница 7: ... Heating 100ºF 100 to 130ºF 5ºF Zoning Target Supply Air Temp for HP Heating 90ºF 85 to 110ºF 1ºF Zoning Supply Air Temp Limit for Cooling 40ºF 35 to 45ºF 2ºF Zoning Supply Air Temp Limit for Gas Electric Heating 140ºF 140 to 160ºF 5ºF Number of stages shown in thermostat is dependent on equipment that is installed Electric heat will bring on 2 elements at a time if available Lock in 2nd stage HP ...

Страница 8: ...l Air Handler Parameter Name Default Parameter Value Setting Increment Equipment Name Air Handler keyboard input screen Electric Heating Airflow nnnn CFM See Note at end of table NOTE CFM Default and Values Settings are dependent on the tonnage of the unit 5CFM High Cooling Airflow nnnn CFM See Note at end of table NOTE CFM Default and Values Settings are dependent on the tonnage of the unit 5CFM ...

Страница 9: ... Control Type Selections available if discharge air temperature sensor is installed fixed cfm and fixed discharge air temperature Low Heating Airflow Low and high heating air flow is dependent on model of indoor unit High Heating Airflow Gas Heat Airflow Settings Heating Airflow Control Type variable capacity furnaces only 0 Fixed CFM 0 1 1 DATS installed 0 Fixed CFM 1 Fixed DAT Low Heating Airflo...

Страница 10: ...p to the closest number on 25 CFM resolution Note 3 All communicating Installer Parameters default CFM values based on DIP switch setting non communicating value are calculated using the CFM conversion tables and rounded up to closest number on 25 CFM resolution Table 7 System Devices Thermostat System Heat Pump Furnace Thermostat system devices To adjust a setting high light it then press Edit ed...

Страница 11: ...re 10 Adjust a Non Communicating Device Setting Humidification How Humidification Mode Works DISPLAY BASIC AND PRECISION These modes allow user control of relative humidity between 15 and 45 These conditions must be met for either mode to operate humidification mode has been enabled and the unit is in HEAT mode and humidification demand exists 24V present at H and DISPLAY mode indicates humidifica...

Страница 12: ...oint Control Humiditrol Comfort Adjust Min De humidification Setpoint edit reset back De humidification Control Mode current value 45 9 39 am Aug 15 2012 4a 4b Humiditrol Comfort Adjust settings are only available on units equipped with a Humiditrol De humidification device resetAll 2b 6 Min De humidification Setpoint Range is 40 to 60 Default is 45 inc 1 cancel save set to 42 5a 5b returns to adj...

Страница 13: ...HUMIDIFICATION DEVICE NOTE OFF MEDIUM and HIGH De humidification modes are also a function of the HVAC system with NO external De humidification devices installed In OFF mode De humidification if off In MEDIUM mode De humidification occurs if these conditions are met and signals are present at specific terminals De humidification has been enabled on installer settings and the unit is in COOL mode ...

Страница 14: ...To adjust a setting highlight it then press Edit System reinstall edit reset De humidification Control Mode current value back Midpoint Overcooling Pre adjustment REQUIREMENTS 1st the device has been installed 2nd from the Add or Remove Non communicating equipment press next 3rd in the Adjust a setting screen configure the device as follows 1 In the system devices list use the arrows 1a to highlig...

Страница 15: ...r only calls If the blower is required to operate while the auxiliary dehumidifier is running a separate wire must be installed from the auxiliary dehumidifier to the indoor unit s G thermostat input that will energize G when the auxiliary dehumidifier is running see wiring diagram on page 37 Auxiliary De humidification is controlled by the thermostat De humidification demand NOTE Refer to HCWH De...

Страница 16: ... furnace about System Furnace Thermostat 2 Stage HP Unit Zoning Control reset All edit System Equipment Name Zoning Target Supply Air Temp C Zoning Target Supply Air Temp fo Zoning Target Supply Air Temper Zoning Target Supply Air Temper Zoning Supply Air Temp Limit for Zoning Supply Air Temp Limit for HP heating lockout time Zoning Target Supply Air temp for Cooling 1 current value edit Zoning Ta...

Страница 17: ...tton to un check desired test 2 Press the start button 4 to run all selected tests or press skip tests 5 to end the test procedure 3 After the tests are completed or you have selected skip test select the exit button to end Blower HP Heat 1st Stage HP Heat 2nd Stage Defrost Now Cooling 1st Stage Cooling 2nd Stage Gas Heat 1st Stage Gas Heat 2nd Stage select all select test to run deselect all skip...

Страница 18: ...to set temp 75 Heat to 72 heat or cool fan is AUTO enter away outdoor temperature 80 system is cooling Wi Fi Zone 1 1 Wi Fi Figure 24 Press Wi FI 2 Press the Wi Fi enable button WI FIL SETTINGS Press to enable disable Wi FI 9 39 am Aug 15 2012 disabled Thermostat is not connected to the Wi FI network WI FI Wi Fi Zone 1 X Figure 25 Enable Wi FI 3 Press next as many times as necessary then press acc...

Страница 19: ...signal strength can be viewed from the thermostat interface Use steps 1 1 Press NETWORK SETTINGS this screen shows a graphical view of buttons representing Wi Fi options OPEN and SECURE wireless networks and a button for adding a network 2 Select the access point that has already been establish and connected too There are two options to select from which are connect and AP info Select AP Info and ...

Страница 20: ...with an Internet connection Please complete your Lennox iComfort registration by clicking the link below Register NOTE if the customer has already setup an account click the Click Here button to access that account Click on the Register link the screen to the left will appear Fill in the User Name and Password fields and check the agree to terms and conditions box Click Create User button A series...

Страница 21: ...r press cancel equipment diagnostics tests alerts setup 9 39 am Aug 15 2012 EXIT confirm cancel 2 1 3 Figure 35 Re Configuration Process If any component of the HVAC system has been changed e g replacing an outdoor sensor reconfiguring the system will be required To begin reconfiguring a system after you have accessed the program from the Lennox logo previous page press the setup button 1 figure 3...

Страница 22: ...ess edit Use arrows to select a temperature between 40 and 55ºF Press save SMOOTH SETBACK RECOVERY SSR SSR is an algorithm designed to smoothly reach a occupied program schedule set point The algorithm looks 2 hours ahead for the occupied program schedule period s set point If the occupied set point requires the system to turn on present temperature below the heat set point or above the cool set p...

Страница 23: ...orter to maintain temperature 4 Tempering Variable Capacity Modulating Furnace SLP98 Dual fuel tempering staged furnace employs no sensor implementation Furnace starts heating at minimum heat rate while defrost is active Testing has shown the entering air is within acceptable limits During defrost the airflow will run at second stage CFM Abbreviations FURN auxiliary heat provided by gas furnace HP...

Страница 24: ... operation control using the following inputs Room temperature History of cycle times how long does it typically take to bring the room temperature to the desired set point Target set point and Differential temperature settings between 1st 4th stage The thermostat uses this information to vary the heating capacity to efficiently satisfy the heating demand The full range of the furnace heating capa...

Страница 25: ...he left side of the system and device alerts screen shows a list of each communicating device discovered in the system and check boxes for selecting each device Or you may use buttons to the right of the System Devices list to select all or deselect all After something has been selected use view active to list all active alerts for selected devices If there are no alerts the display will show Ther...

Страница 26: ...r the transformer maybe overloaded and check 24VAC voltage at the DEVICE The alarm is only cleared by pressing the clear button on the Installer Alerts Tab If the fault persists after check ing the connections replace the unit s control board 34 Critical Thermostat The thermostat does not know the capacity tonnage of the furnace air handler or outdoor unit Please program the correct capacity of th...

Страница 27: ...t door Unit Equipiment Interface Module Damper Control Module The Thermostat furnace air handler or outdoor unit control parameters are corrupted Reconfigure the system Replace the control if heating or cooling is not available 132 Critical Air Handler Damper Control Module The device s control software is corrupted Recycle power If failure re occurs replace the control System reset is required to...

Страница 28: ...off during a heating cycle Check micro amperes of flame sensor using thermostat diagnostics Clean or replace sensor Measure voltage of neutral to ground to ensure good unit ground The alarm fault will clear when a heat call ends successfully 274 Critical Furnace The furnace limit switch has been open for more than 3 minutes The system will go into Watchguard mode Check firing rate and air flow Che...

Страница 29: ...tacts did not close or the relay coil in the electric heat section did not ener gize The air handler will operate on 1st stage electric heat until the issue is re solved Heat section Stage 3 failed Same as Code 351 354 Critical Air Handler There is a problem with the air handler s 4th stage electric heat Either the pilot relay contacts did not close or the relay coil in the electric heat section d...

Страница 30: ...re is higher than the recommended upper limit of 279ºF Discharge line temperature is 279ºF Make sure coil is clean and airflow unobstructed in and out of condenser Check system operating pressures and compare to unit charging charts in installation manual Clears after discharge temperature is 225ºF 415 Critical Outdoor Unit The discharge line temperat ure has been consistently higher than the reco...

Страница 31: ...tdoor unit will stop compressor and fan Anti short cycle is initiated If condition occurs 10 times within an hour system will lockout System will stop To clear disconnect power to outdoor unit and restart 433 Moderate Critical Compressor phase current is too high Error occurs when compressor peak phase current is greater than 28A Inverter will issue code 14 first and slow down to try to reduce the...

Страница 32: ...if demand is still present Alarm clears 5 minutes after fault clears 600 Critical Compressor has been cycled OFF on utility load shedding Load shedding function Provides a method for a local utility company to limit the maximum power level usage of the outdoor unit The feature is activated by applying 24 volts AC power to the L and C terminals on the outdoor control 601 Critical Outdoor unit has b...

Страница 33: ...elect the desired humidifier control mode Basic Precision or Dew Point Basic is the most popular and press the save button Follow the red instructions then exit the system If Humidification Control Mode is not offered as a menu item choice the Humidifier must be added to the iComfort system using the Add or Re move Non communicating equipment screen under the thermostat installer program in the se...

Страница 34: ...tems The adjustable system configuration settings are listed in the equipment button under System In the installer program select the equipment button and choose System from system device and press edit Over 25 installer adjustable settings are provided including balance point humidification control De humidification modes stage differentials and delays 19 During the cooling mode the dis played ai...

Страница 35: ... total length of all connections on the RSBus is limited to 1500ft Wire gauge of RSBus wire is 18 RSBus RSBus ICOMFORT COMMUNICATING INDOOR NON COMMUNICATING OUTDOOR SYSTEM WIRING iComfort Wi Fi Thermostat iComfort by Lennox Air Handler Standard Outdoor Heat Pump STANDARD OUTDOOR HEAT PUMP UNIT 1 OR 2 STAGE iComfort by Lennox AIR HANDLER AHC iComfort Wi Fi THERMOSTAT iComfort by Lennox FURNACE IFC...

Страница 36: ...fort in door unit See iharmony Damper Control Module Installation Instruction for connections to dampers and sensor inputs Damper Control Module DCM DAS NOTE The discharge air sensor is intended to be mounted downstream of the heat exchanger and air conditioning coil It must be placed in free airflow where other accessories such as humidifiers UV lights etc will not interfere with its accuracy Wir...

Страница 37: ...c tions iComfort by Lennox SL280 EL296 FURNACE 48G96 Relay GND IN iComfort enabled outdoor unit iComfort Wi Fi thermostat RSBus For SL290 EL296 see HUMIDIFIER diagram below bottom right 120VAC HUMIDIFIER CONNECTIONS 24VAC OPTIONAL ACCESSORIES WIRING FOR USE WITH ANY ICOMFORT BY LENNOX SYSTEM iComfort by Lennox Furnace or Air Handler HEPA Bypass Filter X2680 HEPA Interlock Kit Pass indoor blower mo...

Страница 38: ... to detect the number of electric heat sections SEE ALSO 506181 01 for complete configuration guide This procedure is applicable only to the CBX32MV XX 230 6 06 and higher and CBX40UHV all models To configure the heat strips so that they will be detected by the thermostat Power must be applied to the air handler but NOT to the thermostat Remove thermostat from base plate or remove wires to thermos...

Страница 39: ... an iComfort enabled heat pump XP17 XP21 and XP25 only 1 Wiring see Communicating System Wiring diagram on page 35 and Optional Accessories Wiring on page 37 for any accessories being installed with the system 4 conductor thermostat wire from the iComfort Wi Fi thermostat to the gas furnace R i i C 4 conductor thermostat wire from the furnace terminal strip to the iComfort enabled HP R i i C Wirin...

Страница 40: ... handler CBX32MV or CBX40UHV with an iComfort enabled heat pump XP17 XP21 or XP25 unit NOTE IMPORTANT Be sure to set up the air handler control for heat strips if used prior to powering up the system and thermostat 1 Configure air handler control AHC for auxiliary heat strips if used 2 Wiring See Communicating System Wiring diagram on page 35 and Optional Accessories Wiring on page 37 for any acce...

Страница 41: ...l fuel system like the ComfortSense 7000 must be selected for this type of application ICOMFORT AIR HANDLER AND NON COMMUNICATING LENNOX CONVENTIONAL AIR CONDITIONER An iComfort air handler CBX32MV or CBX40UHV with a conventional non communicating AC unit NOTE IMPORTANT Be sure to set up the air handler control for heat strips if used prior to powering up the system and thermostat 1 Configure air ...

Страница 42: ... Outdoor Temp Display From the Home screen press press for more area and select the HELP icon Press the user preferences box and scroll down to Outdoor Temp Display Press the modify button and use the up down arrows to select On or Off and then press the save button Press done to return to the Home screen ICOMFORT ENABLED EQUIPMENT INTERFACE MODULE The iComfort Equipment Interface Module EIM can b...

Страница 43: ... 42 60 rev 02 thru 04 AND XC17 36 48 rev 02 thru 05 65W71 605341 03 XC17 24 30 42 60 rev 05 or later AND XC17 36 48 rev 06 or later 87W24 96W55 103369 01 XP17 24 30 rev 02 thru 05 AND XP17 36 42 48 60 rev 02 thru 04 65W73 605341 05 XP17 24 30 rev 06 or later AND XP17 36 42 48 60 rev 05 or later 87W24 96W55 103369 01 XP19 24 36 48 60 rev 06 or later 87W24 96W55 103369 01 XC21 24 36 48 60 rev 05 thr...

Отзывы: