background image

iComfort Wi-Fi

®

 

7-Day Programmable Communicating Thermostat

Page 15

DE-HUMIDIFICATION SETTINGS  — FEATURE SCREEN

1. From the 

Main Screen

, press the 

right arrow

 icon to go the the 

Features

screen.

2. From the 

Features 

screen, select 

system systems

.

3. Touch  the 

ClimateIQ 

setting  button.  Available  options  when  selected  are

selection for DRY, MODERATE and HUMID.

4. Selecting  HUMID  bring  on  the 

set-to

  button.  When  you  touch  the 

set-to

button, the arrows appear, allowing you to change to the desired de-humidifier
percentage setting

SYSTEM SETTINGS

heating

mode

COMFORT

humidifier

is ON

ClimateIQ

setting

MOD

humidifier

display

 is ON

Appears only when

heat pump is

present

humidification

settings

De-humidification settings

(default is DRY)

(default  is  ON)

(default  is  ON)

Select  the  humidity
level  that  matches
your environment

9:39 am Aug 15, 2012

?

Wi-Fi

35

%

set to

40

%

set  to

Figure 17. Humidifier Controls (Communicating Outdoor Unit)

HEATING MODE (XP25 ONLY) — CLIMATE IQ™

This  technology  optimizes  De-humidification  settings  for  specific  climates  to
improve home comfort during cooling or heating operations.

Two climate settings are available:

Comfort 

  The  system  reduces  indoor  airflow,  increasing  supply  air

temperature.

Normal 

 Standard system operation.

COOLING MODE — CLIMATE IQ™

Three climate settings are available:

Dry 

 The system supplies higher indoor airflow at all compressor capacities,

increasing efficiency by operating at a higher sensible to total ratio.

Moderate 

 The system supplies indoor airflow that balances efficiency and

comfort.

Humid 

  The  system  supplies  lower  indoor  airflow  at  all  compressor

capacities, improving humidity removal by operating at a lower sensible to
total ratio.

How De-humidification Mode Works

DRY, MODERATE AND HUMID 

—These modes allow user control of

relative humidity between 40% and 60% RH. These conditions must be
met for either mode to operate:

de-humidification mode has been enabled, and

the unit is in COOL mode, and

-de-humidification demand exists (0V present at H), and

MODERATE

 mode also requires presence of cooling demand [Y for HP

heat, or W for gas heat (W may be energized with G de-energized)].

Humiditrol

®

 or Auxiliary Dehumidifier

 mode requires:

NOTE - Systems using icomfort

t

 and a de-humidifier - “Dehum” jump

er on furnace/air handler control does not need to be cut when using
with a iComfort Wi-Fi

®

 thermostat.

Wi-Fi is operational or outdoor sensor is installed and set up

de-humidification has been enabled on installer settings, and

the unit is in COOL mode, (or if in AUTO, at least one thermostat
cooling call made prior to the De-humidification demand), and

a de-humidification demand exists (RH above set point), and

outdoor temp. below 95°F; indoor temp. above 65°F, and

for 

HUMIDITROL

, adjust Humiditrol

®

 comfort parameters as fol

lows:

MAX

 adj. - Indoor temp > 2°F above heating set point

MID

 adj. - Indoor temp > 

MIN

 adj. - Indoor temp > 2°F below cooling set point

HEAT se COOL setpoint

2

2

AUXILIARY DEHUMIDIFIER — STAND-ALONE DEHUMIDIFIER

When this option is selected, De-humidification will be allowed under the following
conditions, provided 

there is NO call for humidification

:

In the absence of heating or cooling calls, or

Simultaneous with blower only calls.

If the blower is required to operate while the auxiliary dehumidifier is running, a
separate wire must be installed from the auxiliary dehumidifier to the indoor unit's G
thermostat input that will energize G when the auxiliary dehumidifier is running (see
wiring diagram on page 37).

Auxiliary  De-humidification  is  controlled  by  the  thermostat  De-humidification
demand.

NOTE  -  Refer  to  HCWH  Dehumidifier  Installation  Instructions  for  installation
recommendations.

HOW DE-HUMIDIFICATION MODE WORK  — NO EXTERNAL
DE-HUMIDIFICATION DEVICE

NOTE - 

OFF, MEDIUM

 and 

HIGH 

De-humidification modes are also a function of the

HVAC system with NO external De-humidification devices installed.

In 

OFF

 mode, De-humidification if off.

In 

MEDIUM

 mode, De-humidification occurs if these conditions are met and signals are

present at specific terminals:

De-humidification has been enabled on installer settings, and

the unit is in COOL mode, and

De-humidification demand exists (RH above set point), and

cooling demand exists (Y1 energized).

In 

HIGH

 mode, De-humidification occurs if all BASIC conditions are true, except cooling

demand may or may not be present. Also note that:

Maximum overcool from cooling set point is 2ºF.

Deadband

 temperature is limited to a minimum of 5ºF (instead of 3ºF in 

DRY

or 

MODERATE

 modes) because of 2ºF overcooling.

G71MPP OR SLP98 FURNACE SETTING ADJUSTMENT

If your iComfort Wi-Fi

®

 thermostat is being used with a G71MPP or SLP98 furnace

and is set to variable-capacity mode of operation (the icomfort

 default with these

units), the thermostat's settings for stage timers are ignored (even if shown enabled
in the thermostat). The stage timer will be used on the cooling side for other cooling
units except the XC/XP25 where they are not used. The furnace software sets and
controls the firing rates. The only other controlling factor is the stage temperature
differentials. In Load-Tracking Variable Capacity (default for these furnaces), both
stage timers and temperature differentials are ignored.

ZONING CONTROL SETTINGS

 

NOTE - Skip if no zoning control device is installed.

A. Heat/Cool Changeover

The following is an example of how the system operates during a heating  / cooling
changeover.

When the system is satisfying a call from zone 1 for heating and receives a call for
cooling from zone 2, the following will occur:

Then system will continue to fulfill the demand from zone 1 until satisfied, or
a maximum time of 20 minutes has occurred.

If after 20 minutes the system is still operating based on satisfying the heating
demand from zone 1, the system will terminate that demand. 

The system will then shut system down for five (5) minutes. This will allow for
system temperatures and operating pressures to stabilize.

After a five 5 minute delay the system will begin operations to satisfied the
cooling demand from zone 2.

The system will continue to operate in this matter each time it receives a zone call
that is opposite of the current mode of operation (heating or cooling).

B. Damper Operation

Cooling Operation  Conventional Heat/Cool and Heat Pump Systems

When a in-zone thermostat makes a demand for cooling, the zone damper opens
and the cooling equipment begins operating.

Cooling demand is terminated when:

1. All zone demands for cooling are terminated.

2. The demand has exceeded the heat/cool changeover

 

time limit (20minutes)

while a heat demand exists.

Содержание iComfort CBX32MV-06

Страница 1: ... or Auxiliary Dehumidifier 5 Adjusting Equipment Parameters 6 Adjusting Humidification and De humidification Settings with Non Communicating Outdoor Units 11 Adjusting Humidification and De humidification Settings with Communicating Outdoor Units 13 Adjusting Zoning Control Settings 15 Using the Tests Diagnostics Features 17 Connecting to a Home Wi Fi Network 18 Registering the Thermostat 19 Accou...

Страница 2: ...oling humidification and De humidification without user involvement OUTDOOR TEMPERATURE SENSOR All Lennox branded communicating outdoor units contain a built in outdoor temperature sensor INSTALLATION AND SETUP COMMUNICATION ERROR SCREEN During initial thermostat start up if the following screen appears see figure 1 this will indicate that the thermostat has been incorrectly wired or has shorted w...

Страница 3: ...tatus remotely or receive email alerts when there is a problem no yes WARNING The dealer number is your Lennox account number Enter the entire dealer number including the letters and numbers e A12345 If you do not know your dealer number please contact your Lennox representative Are you sure you want to proceed Figure 5 Dealer Number Warning The following table lists all of the installer configura...

Страница 4: ...ot icomfort enabled you must be at the Add or Remove Non communicating equipment screen 1 Press the yes button on this screen see 1 2 In the non communicating device list screen use the arrows 2a to highlight Outdoor Unit Type and press edit 2b 3 Touch one of the radio buttons 3a to select a 1 or 2 Stage AC Unit or a 1 or 2 Stage HP Unit press save 3b 4 Use arrows 4a to highlight any red colored t...

Страница 5: ...icating equipment 4a 4b System Heat Pump Furnace Thermostat Bypass 24VAC Humidifier 5b 3a Figure 7 Add Non Communicating Device Humidifier ADDING HUMIDITROL OR AN AUXILIARY DEHUMIDIFIER Before adding a dehumidifier be sure that the dehumidifier is wired to the furnace or air handler control as shown on the Optional Accessories wiring diagram see page 37 the entire system is wired powered up and th...

Страница 6: ...ing highlight it then press Edit System 9 39 am Aug 15 2012 edit next back about resetAll Parameter Name Default Parameter Value Setting Increment Equipment Name keyboard input screen Filter 1 Timer Selection Calendar Time Calendar Time Run Time Filter 2 Timer Selection Calendar Time Calendar Time Run Time UV Bulb Timer Selection Calendar Time Calendar Time Run Time Humidifier Pad Timer Selection ...

Страница 7: ... Heating 100ºF 100 to 130ºF 5ºF Zoning Target Supply Air Temp for HP Heating 90ºF 85 to 110ºF 1ºF Zoning Supply Air Temp Limit for Cooling 40ºF 35 to 45ºF 2ºF Zoning Supply Air Temp Limit for Gas Electric Heating 140ºF 140 to 160ºF 5ºF Number of stages shown in thermostat is dependent on equipment that is installed Electric heat will bring on 2 elements at a time if available Lock in 2nd stage HP ...

Страница 8: ...l Air Handler Parameter Name Default Parameter Value Setting Increment Equipment Name Air Handler keyboard input screen Electric Heating Airflow nnnn CFM See Note at end of table NOTE CFM Default and Values Settings are dependent on the tonnage of the unit 5CFM High Cooling Airflow nnnn CFM See Note at end of table NOTE CFM Default and Values Settings are dependent on the tonnage of the unit 5CFM ...

Страница 9: ... Control Type Selections available if discharge air temperature sensor is installed fixed cfm and fixed discharge air temperature Low Heating Airflow Low and high heating air flow is dependent on model of indoor unit High Heating Airflow Gas Heat Airflow Settings Heating Airflow Control Type variable capacity furnaces only 0 Fixed CFM 0 1 1 DATS installed 0 Fixed CFM 1 Fixed DAT Low Heating Airflo...

Страница 10: ...p to the closest number on 25 CFM resolution Note 3 All communicating Installer Parameters default CFM values based on DIP switch setting non communicating value are calculated using the CFM conversion tables and rounded up to closest number on 25 CFM resolution Table 7 System Devices Thermostat System Heat Pump Furnace Thermostat system devices To adjust a setting high light it then press Edit ed...

Страница 11: ...re 10 Adjust a Non Communicating Device Setting Humidification How Humidification Mode Works DISPLAY BASIC AND PRECISION These modes allow user control of relative humidity between 15 and 45 These conditions must be met for either mode to operate humidification mode has been enabled and the unit is in HEAT mode and humidification demand exists 24V present at H and DISPLAY mode indicates humidifica...

Страница 12: ...oint Control Humiditrol Comfort Adjust Min De humidification Setpoint edit reset back De humidification Control Mode current value 45 9 39 am Aug 15 2012 4a 4b Humiditrol Comfort Adjust settings are only available on units equipped with a Humiditrol De humidification device resetAll 2b 6 Min De humidification Setpoint Range is 40 to 60 Default is 45 inc 1 cancel save set to 42 5a 5b returns to adj...

Страница 13: ...HUMIDIFICATION DEVICE NOTE OFF MEDIUM and HIGH De humidification modes are also a function of the HVAC system with NO external De humidification devices installed In OFF mode De humidification if off In MEDIUM mode De humidification occurs if these conditions are met and signals are present at specific terminals De humidification has been enabled on installer settings and the unit is in COOL mode ...

Страница 14: ...To adjust a setting highlight it then press Edit System reinstall edit reset De humidification Control Mode current value back Midpoint Overcooling Pre adjustment REQUIREMENTS 1st the device has been installed 2nd from the Add or Remove Non communicating equipment press next 3rd in the Adjust a setting screen configure the device as follows 1 In the system devices list use the arrows 1a to highlig...

Страница 15: ...r only calls If the blower is required to operate while the auxiliary dehumidifier is running a separate wire must be installed from the auxiliary dehumidifier to the indoor unit s G thermostat input that will energize G when the auxiliary dehumidifier is running see wiring diagram on page 37 Auxiliary De humidification is controlled by the thermostat De humidification demand NOTE Refer to HCWH De...

Страница 16: ... furnace about System Furnace Thermostat 2 Stage HP Unit Zoning Control reset All edit System Equipment Name Zoning Target Supply Air Temp C Zoning Target Supply Air Temp fo Zoning Target Supply Air Temper Zoning Target Supply Air Temper Zoning Supply Air Temp Limit for Zoning Supply Air Temp Limit for HP heating lockout time Zoning Target Supply Air temp for Cooling 1 current value edit Zoning Ta...

Страница 17: ...tton to un check desired test 2 Press the start button 4 to run all selected tests or press skip tests 5 to end the test procedure 3 After the tests are completed or you have selected skip test select the exit button to end Blower HP Heat 1st Stage HP Heat 2nd Stage Defrost Now Cooling 1st Stage Cooling 2nd Stage Gas Heat 1st Stage Gas Heat 2nd Stage select all select test to run deselect all skip...

Страница 18: ...to set temp 75 Heat to 72 heat or cool fan is AUTO enter away outdoor temperature 80 system is cooling Wi Fi Zone 1 1 Wi Fi Figure 24 Press Wi FI 2 Press the Wi Fi enable button WI FIL SETTINGS Press to enable disable Wi FI 9 39 am Aug 15 2012 disabled Thermostat is not connected to the Wi FI network WI FI Wi Fi Zone 1 X Figure 25 Enable Wi FI 3 Press next as many times as necessary then press acc...

Страница 19: ...signal strength can be viewed from the thermostat interface Use steps 1 1 Press NETWORK SETTINGS this screen shows a graphical view of buttons representing Wi Fi options OPEN and SECURE wireless networks and a button for adding a network 2 Select the access point that has already been establish and connected too There are two options to select from which are connect and AP info Select AP Info and ...

Страница 20: ...with an Internet connection Please complete your Lennox iComfort registration by clicking the link below Register NOTE if the customer has already setup an account click the Click Here button to access that account Click on the Register link the screen to the left will appear Fill in the User Name and Password fields and check the agree to terms and conditions box Click Create User button A series...

Страница 21: ...r press cancel equipment diagnostics tests alerts setup 9 39 am Aug 15 2012 EXIT confirm cancel 2 1 3 Figure 35 Re Configuration Process If any component of the HVAC system has been changed e g replacing an outdoor sensor reconfiguring the system will be required To begin reconfiguring a system after you have accessed the program from the Lennox logo previous page press the setup button 1 figure 3...

Страница 22: ...ess edit Use arrows to select a temperature between 40 and 55ºF Press save SMOOTH SETBACK RECOVERY SSR SSR is an algorithm designed to smoothly reach a occupied program schedule set point The algorithm looks 2 hours ahead for the occupied program schedule period s set point If the occupied set point requires the system to turn on present temperature below the heat set point or above the cool set p...

Страница 23: ...orter to maintain temperature 4 Tempering Variable Capacity Modulating Furnace SLP98 Dual fuel tempering staged furnace employs no sensor implementation Furnace starts heating at minimum heat rate while defrost is active Testing has shown the entering air is within acceptable limits During defrost the airflow will run at second stage CFM Abbreviations FURN auxiliary heat provided by gas furnace HP...

Страница 24: ... operation control using the following inputs Room temperature History of cycle times how long does it typically take to bring the room temperature to the desired set point Target set point and Differential temperature settings between 1st 4th stage The thermostat uses this information to vary the heating capacity to efficiently satisfy the heating demand The full range of the furnace heating capa...

Страница 25: ...he left side of the system and device alerts screen shows a list of each communicating device discovered in the system and check boxes for selecting each device Or you may use buttons to the right of the System Devices list to select all or deselect all After something has been selected use view active to list all active alerts for selected devices If there are no alerts the display will show Ther...

Страница 26: ...r the transformer maybe overloaded and check 24VAC voltage at the DEVICE The alarm is only cleared by pressing the clear button on the Installer Alerts Tab If the fault persists after check ing the connections replace the unit s control board 34 Critical Thermostat The thermostat does not know the capacity tonnage of the furnace air handler or outdoor unit Please program the correct capacity of th...

Страница 27: ...t door Unit Equipiment Interface Module Damper Control Module The Thermostat furnace air handler or outdoor unit control parameters are corrupted Reconfigure the system Replace the control if heating or cooling is not available 132 Critical Air Handler Damper Control Module The device s control software is corrupted Recycle power If failure re occurs replace the control System reset is required to...

Страница 28: ...off during a heating cycle Check micro amperes of flame sensor using thermostat diagnostics Clean or replace sensor Measure voltage of neutral to ground to ensure good unit ground The alarm fault will clear when a heat call ends successfully 274 Critical Furnace The furnace limit switch has been open for more than 3 minutes The system will go into Watchguard mode Check firing rate and air flow Che...

Страница 29: ...tacts did not close or the relay coil in the electric heat section did not ener gize The air handler will operate on 1st stage electric heat until the issue is re solved Heat section Stage 3 failed Same as Code 351 354 Critical Air Handler There is a problem with the air handler s 4th stage electric heat Either the pilot relay contacts did not close or the relay coil in the electric heat section d...

Страница 30: ...re is higher than the recommended upper limit of 279ºF Discharge line temperature is 279ºF Make sure coil is clean and airflow unobstructed in and out of condenser Check system operating pressures and compare to unit charging charts in installation manual Clears after discharge temperature is 225ºF 415 Critical Outdoor Unit The discharge line temperat ure has been consistently higher than the reco...

Страница 31: ...tdoor unit will stop compressor and fan Anti short cycle is initiated If condition occurs 10 times within an hour system will lockout System will stop To clear disconnect power to outdoor unit and restart 433 Moderate Critical Compressor phase current is too high Error occurs when compressor peak phase current is greater than 28A Inverter will issue code 14 first and slow down to try to reduce the...

Страница 32: ...if demand is still present Alarm clears 5 minutes after fault clears 600 Critical Compressor has been cycled OFF on utility load shedding Load shedding function Provides a method for a local utility company to limit the maximum power level usage of the outdoor unit The feature is activated by applying 24 volts AC power to the L and C terminals on the outdoor control 601 Critical Outdoor unit has b...

Страница 33: ...elect the desired humidifier control mode Basic Precision or Dew Point Basic is the most popular and press the save button Follow the red instructions then exit the system If Humidification Control Mode is not offered as a menu item choice the Humidifier must be added to the iComfort system using the Add or Re move Non communicating equipment screen under the thermostat installer program in the se...

Страница 34: ...tems The adjustable system configuration settings are listed in the equipment button under System In the installer program select the equipment button and choose System from system device and press edit Over 25 installer adjustable settings are provided including balance point humidification control De humidification modes stage differentials and delays 19 During the cooling mode the dis played ai...

Страница 35: ... total length of all connections on the RSBus is limited to 1500ft Wire gauge of RSBus wire is 18 RSBus RSBus ICOMFORT COMMUNICATING INDOOR NON COMMUNICATING OUTDOOR SYSTEM WIRING iComfort Wi Fi Thermostat iComfort by Lennox Air Handler Standard Outdoor Heat Pump STANDARD OUTDOOR HEAT PUMP UNIT 1 OR 2 STAGE iComfort by Lennox AIR HANDLER AHC iComfort Wi Fi THERMOSTAT iComfort by Lennox FURNACE IFC...

Страница 36: ...fort in door unit See iharmony Damper Control Module Installation Instruction for connections to dampers and sensor inputs Damper Control Module DCM DAS NOTE The discharge air sensor is intended to be mounted downstream of the heat exchanger and air conditioning coil It must be placed in free airflow where other accessories such as humidifiers UV lights etc will not interfere with its accuracy Wir...

Страница 37: ...c tions iComfort by Lennox SL280 EL296 FURNACE 48G96 Relay GND IN iComfort enabled outdoor unit iComfort Wi Fi thermostat RSBus For SL290 EL296 see HUMIDIFIER diagram below bottom right 120VAC HUMIDIFIER CONNECTIONS 24VAC OPTIONAL ACCESSORIES WIRING FOR USE WITH ANY ICOMFORT BY LENNOX SYSTEM iComfort by Lennox Furnace or Air Handler HEPA Bypass Filter X2680 HEPA Interlock Kit Pass indoor blower mo...

Страница 38: ... to detect the number of electric heat sections SEE ALSO 506181 01 for complete configuration guide This procedure is applicable only to the CBX32MV XX 230 6 06 and higher and CBX40UHV all models To configure the heat strips so that they will be detected by the thermostat Power must be applied to the air handler but NOT to the thermostat Remove thermostat from base plate or remove wires to thermos...

Страница 39: ... an iComfort enabled heat pump XP17 XP21 and XP25 only 1 Wiring see Communicating System Wiring diagram on page 35 and Optional Accessories Wiring on page 37 for any accessories being installed with the system 4 conductor thermostat wire from the iComfort Wi Fi thermostat to the gas furnace R i i C 4 conductor thermostat wire from the furnace terminal strip to the iComfort enabled HP R i i C Wirin...

Страница 40: ... handler CBX32MV or CBX40UHV with an iComfort enabled heat pump XP17 XP21 or XP25 unit NOTE IMPORTANT Be sure to set up the air handler control for heat strips if used prior to powering up the system and thermostat 1 Configure air handler control AHC for auxiliary heat strips if used 2 Wiring See Communicating System Wiring diagram on page 35 and Optional Accessories Wiring on page 37 for any acce...

Страница 41: ...l fuel system like the ComfortSense 7000 must be selected for this type of application ICOMFORT AIR HANDLER AND NON COMMUNICATING LENNOX CONVENTIONAL AIR CONDITIONER An iComfort air handler CBX32MV or CBX40UHV with a conventional non communicating AC unit NOTE IMPORTANT Be sure to set up the air handler control for heat strips if used prior to powering up the system and thermostat 1 Configure air ...

Страница 42: ... Outdoor Temp Display From the Home screen press press for more area and select the HELP icon Press the user preferences box and scroll down to Outdoor Temp Display Press the modify button and use the up down arrows to select On or Off and then press the save button Press done to return to the Home screen ICOMFORT ENABLED EQUIPMENT INTERFACE MODULE The iComfort Equipment Interface Module EIM can b...

Страница 43: ... 42 60 rev 02 thru 04 AND XC17 36 48 rev 02 thru 05 65W71 605341 03 XC17 24 30 42 60 rev 05 or later AND XC17 36 48 rev 06 or later 87W24 96W55 103369 01 XP17 24 30 rev 02 thru 05 AND XP17 36 42 48 60 rev 02 thru 04 65W73 605341 05 XP17 24 30 rev 06 or later AND XP17 36 42 48 60 rev 05 or later 87W24 96W55 103369 01 XP19 24 36 48 60 rev 06 or later 87W24 96W55 103369 01 XC21 24 36 48 60 rev 05 thr...

Отзывы: