507152-01
7/2013
Page 8
Table 4. System Devices > Heat Pump
System
Heat Pump
Furnace
Thermostat
system devices
To adjust a setting, high
light it, then press Edit
edit
next
back
about
resetAll
Heat Pump
Parameter Name:
Default
Parameter Value Setting
Increment
Equipment Name
Outdoor Unit
(keyboard input screen = up to 35 characters in string)
—
Compressor Short Cycle Delay
300 Seconds
60 to 300 Seconds
60 Sec
Defrost Termination Temp
50ºF
50ºF to 100ºF
10ºF
Compressor Shift Delay On/Off
On
On, Off
—
High Normal Cooling Airflow (XP25 only)
1600
450 to 2150
25
Low Normal Cooling Airflow (XP25 only)
750
450 to 2150
25
High Normal HP Heating Airflow (XP25 only)
1600
450 to 2150
25
Low Normal HP Heating Airflow (XP25 only)
750
450 to 2150
25
Dehum Airflow Adjustment Adder
0
0 to 30
1
Table 5. System Devices > Air Handler
System
Heat Pump
Air Handler
Thermostat
system devices
To adjust a setting,
highlight it, then press
Edit
edit
next
back
about
resetAll
Air Handler
Parameter Name:
Default
Parameter Value Setting
Increment
Equipment Name
Air Handler
(keyboard input screen)
—
Electric Heating Airflow
nnnn CFM (See Note at
end of table)
NOTE: CFM Default and Values Settings
are dependent on the tonnage of the unit
5CFM
High Cooling Airflow
nnnn CFM (See Note at
end of table)
NOTE: CFM Default and Values Settings
are dependent on the tonnage of the unit
5CFM
Airflow Profile - Cooling
1
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min;
OFF:50%/30s
—
Continuous Indoor Blower Airflow
nnnn CFM (See Note at
end of table)
NOTE: CFM Default and Values Settings
are dependent on the tonnage of the unit
10CFM
Heating Indoor Blower OFF Delay
10 sec
0 to 10 Seconds
1 sec
Heating Indoor Blower ON Delay
0 sec
0 to 5 Seconds
1 sec
Cooling Indoor Blower OFF Delay
0 sec
0 to 30 Seconds
2 sec
Cooling Indoor Blower ON Delay
2 sec
0 to 10 Seconds
1 sec
Note
All communicating Installer Parameters default CFM values based on DIP switch setting (non-communicating value) are calculated using the CFM
conversion tables and rounded up to closest number on 25 CFM resolution.