507152-01
7/2013
Page 6
ADJUSTING SYSTEM DEVICES SETTINGS
1. Press
any component listed under system devices
to change specific communicating equipment parameters and edit details of devices in the system.
2. Use the arrows to highlight a setting and then press
edit
(figure 9
A
). In the example, the low heating airflow is changed from the default (400) to 325 (figure 9
B)
.
After changing, press
save
. (note the current value has changed; figure 9
C
). Some changes may affect other settings and, if so, those affected will appear in red
and require changing/saving to clear the red settings.
3. When finished, press
back
; equipment parameters screen then press
next
. “Select tests to run screen appears”; either run tests as before or press
skip tests
.
9:39 am Aug 15, 2012
System
edit
back
reset All
current value:
400
Low Heating Airflow
Equipment Name
Heating Airflow Control Type
Low Heating Airflow
High Heating Airflow
High Cooling Airflow
Airflow Profile - Cooling
High HP Airflow
Continuous Indoor Blower Airflow
Heating Indoor Blower OFF Delay
9:39 am Aug 15, 2012
System
edit
back
Reset All
current value:
325
Low Heating Airflow
Equipment Name
Heating Airflow Control Type
Low Heating Airflow
High Heating Airflow
High Cooling Airflow
Airflow Profile - Cooling
High HP Airflow
Continuous Indoor Blower Airflow
Heating Indoor Blower OFF Delay
Low Heating Airflow
Range is 325 to 450
Default is 400, inc: 25
cancel
save
set-to
325
Figure 9. Edit Equipment Details
The following tables list the system devices settings available from the installer setup screens.
Table 2. System Devices > System
system devices
System
Heat Pump
Furnace
Thermostat
To adjust a setting,
highlight it, then
press Edit
System
9:39 am Aug 15, 2012
edit
next
back
about
resetAll
Parameter Name:
Default
Parameter Value Setting
Increment
Equipment Name
—
(keyboard input screen)
—
Filter 1 Timer Selection
Calendar Time
Calendar Time, Run Time
—
Filter 2 Timer Selection
Calendar Time
Calendar Time, Run Time
—
UV Bulb Timer Selection
Calendar Time
Calendar Time, Run Time
—
Humidifier Pad Timer Selection
Calendar Time
Calendar Time, Run Time
—
PureAir
Timer Selection
Calendar Time
Calendar Time, Run Time
—
Smooth Setback Recovery
Enabled
Enabled, Disabled
—
Electric Heat Control Mode
Standard
Standard, Evenheat
—
EvenHeat Discharge Temp
85ºF
85ºF to 130ºF
15ºF
Gas Heat Control Mode
Staged
Staged, Variable Capacity, Load Tracking
Variable Capacity
—
Number of Gas Heating Stages (SLP98V only) (staged selection)
4
1, 2, 3 or 4
—
Modulating Gas Heating Steady State PI (SLP98V only)
Standard
Less Aggressive, More Aggressive, Standard
—
Modulating Gas Heat Step Change PI (SLP98V only)
Standard
Less Aggressive, More Aggressive, Standard
—
Modulating HP Heating Cycles Per Hour (XP25 only)
4.0
3.0 to 6.0
0.5
Modulating HP Electric Heating Switching Point (XP25 only)
1.0
0.0 to 2.0
0.25
Modulating HP Heating Steady State PI Gain (XP25 only)
Standard
Less Aggressive, More Aggressive, Standard
—
Modulating HP Heating Step Change PI Gain (XP25 only)
Standard
Less Aggressive, More Aggressive, Standard
—
Modulating Cooling Steady State PI Gain (XC25 and XP25 only)
Less
Aggressive
Less Aggressive, More Aggressive, Standard
—
Modulating Cooling Step Change PI Gain (XC25 and XP25 only)
Less
Aggressive
Less Aggressive, More Aggressive, Standard
—
Modulating Cooling Cycles Per Hour (XC25 and XP25 only)
4.0
3.0 to 6.0
0.5
Auto Changeover - Temp Dead-band
5ºF
3 to 9ºF
1ºF
Max Heat Set point
90ºF
40 to 90ºF
1ºF
Min Cool Set point
60ºF
60 to 99ºF
1ºF
Heat Cool Stages Lock In
60ºF
60 to 99ºF
1ºF