KP07 VDU CONSOLE
All the instructions which follow can be adjusted via the "modification" mode.
III.12.a. Water temperature instructions
The screen shown below corresponds to the case of a liquid cooler. There is a similar screen for heat pumps.
III.12.b. Control parameters for condenser ventilation
Temperature difference
on chilled water
(T input - T output)
Minimum chilled
water temperature
Chilled water
setting A
Chilled water
setting B
Minimum evaporation
temperature
Upper pressure limit
for increasing
ventilation stages
Lower pressure
limit for decreasing
ventilation stages
Timing for increasing or
decreasing by one
ventilation stage