EXCESS HIGH TEMPERATURE
Logical variable :
DHPmn
Incident codes KP02 :
mn5
KP07 icon :
Description
The high pressure safety cut-out on compressor mn PHPmn has tripped..
Action
F
Immediate halt of compressor mn.
F
The fault is displayed on the screen.
F
The remote fault report is delayed for 6 minutes.
Resetting
The first 2 faults are reset
automatically
After this , the compressor mn can only be started after a
manual
reset.
Note :
Counters for " high pressure" failures TOHPmn are all
reset to zero daily at 6 pm
, on condition that
the maximum number of authorised faults has not been reached.
Trouble-shooting
Solution
Condenser clogged.
Fault on parameter settings for regulation of
condensation.
Malfunction of liquid solenoid valve.
Dehydrator clogged.
Wiring fault or high pressure safety cut-out wrongly
set
Clean condenser
Check parameter settings
Check operation of solenoid valve.
Replace the dehydrator
Check setting and wiring of high pressure safety cut-
out.