V2.2
-00
30
LOW PRESSURE INSUFFICIENT
Logical variable :
DBPn
Incident codes KP02 :
n1
KP07 icon :
Description
Case
¶
: No compressor on circuit n is working. The liquid valve has been open for 2 minutes, but low pressure
remains lower than safety limits.
Case
·
: A compressor on circuit n has been operating for more than 2 minutes. The liquid valve is open and
the expansion valve bypass valve (if applicable) has been closed for 1 minute, but low pressure is
insufficient.
Reminder
: The units with an expansion valve bypass valve are those fitted with the "all seasons"
option and thermostatic expansion valves.
Case
¸
: A compressor on circuit n has been operating for over 6 minutes, all other compressors in service on
the circuit have been operating for at least 2 minutes and insufficient low pressure is detected
Action
F
If circuit n is not in operation, start-up has not been authorised. If it is in operation, it stops immediately.
F
The fault is displayed on the screen.
F
The remote fault report is delayed for 6 minutes.
Resetting
Case
¶
&
·
:
Three automatic fault resets
are allowed daily. After this, circuit n can only be restarted
after manual resetting.
Case
¸
:
Resetting is
manual
.
Note
:
"Low pressure" failure counters TOBPn are all
reset to zero daily at 6 pm
, on condition that the
maximum number of faults authorised has not been reached.
Trouble-shooting
Solution
Insufficient circuit load.
Malfunction of the liquid solenoid valve.
Malfunction of expansion valve.
Dehydrator clogged.
Complete the load.
Check solenoid valve operation.
Check expansion valve operation.
Change dehydrator.