FAN CIRCUIT BREAKERS TRIPPED
Logical variable :
DELECV
Incident codes KP02 :
90
KP07 icon :
Description
One or more thermomagnetic circuit breakers protecting the air condenser fans are tripped. (ELECV = 0).
Action
F
The fault is displayed on the screen.
F
The remote fault report is delayed for 6 minutes.
Resetting
The fault is reset
automatically
once all the fan circuit breakers are reset.
Trouble-shooting
Solution
Bad connection or connections too tight.
Circuit breakers wrongly set.
Check connections.
Set protections according to the rated current for fans.