SENSOR OR DETECTOR FAULTS
Logical variable :
DSONDEn
Incident codes KP02 :
n6
KP07 icon :
Description
One or more temperature sensors or pressure detectors installed on circuit n are either in short-circuit, broken
or disconnected.
Sensor or detector involved
Condition for occurrence of fault
Suction temperature sensor
TASPn
≤
-40°C
Internal sensor on electronic expansion
1000 U
≤
RDETn
≤
50 U
Low pressure detector
BPn
≤
0,5 bars
High pressure detector
HPn
≤
0,5 bars
Note :
All these sensors and detectors are not necessarily present on the same machine.
Action
F
Immediate halt of circuit n.
F
The fault is displayed on the screen.
F
The remote fault report is delayed for 6 minutes.
Resetting
Circuit n can only be restarted after
manual
resetting and correct reading of all detectors and sensors.
Trouble-shooting
Solution
Sensor or detector fault.
Wiring fault or disconnection of a sensor or detector.
Replace the element.
Check sensor and detector connections