ABSENCE OF 230V SUPPLY WITH BACKUP
Logical variable :
DPT230V
Incident codes KP02 :
7
KP07 icon :
Description
The supply presence voltage relay is tripped (PT230V = 0).
The compressor casing resistors and the anti-freeze resistors on the hydraulic circuit are no longer fed.
Action
F
Immediate machine halt.
F
The fault is displayed on the screen.
F
The remote fault report is delayed for 6 minutes.
Resetting
The machine restarts
automatically
20 seconds after the 230 V supply has been restored.
Trouble-shooting
Solution
Wiring fault on 230 V supply.
Wiring fault on voltage presence relay.
Vérifier les connexions et la tension de l'alimentation
230 V qui arrive sur la machine.
Vérifier le câblage du relais de présence tension.