VACUUM SUCTION FAILURE
Logical variable :
DPUMPDn
Incident codes KP02 :
n5
KP07 icon :
Description
For
2 minutes
, a compressor on circuit n is in operation and the liquid solenoid is not connected, but low
pressure is still below minimum.
Action
F
Immediate halt of circuit n.
F
The fault is displayed on the screen.
F
The remote fault report is delayed for 6 minutes.
Resetting
The first 2 faults are
automatically
reset after
2 minutes
.
After this, circuit n can only be restarted after a
manual
reset.
Note :
Counters of “pump down” failures TOPUMPDn are all
reset to zero daily at 6 pm
, on condition that the
maximum number of authorised faults has not been reached.
Trouble-shooting
Solution
Liquid solenoid blocked open by foreign matter.
Change the solenoid valve.