V2.2
-00
19
MANAGEMENT OF UNITS IN PARALLEL
Function
To provide staging of units in order to adjust the temperature of the cooled fluid as closely as possible to the set
point.
Description
¶
Management of the installation by an independent CPU card (recommended configuration)
General regulation is by a KP01 independent of those which directly control the units. Dialogue between the
cards is by hard contact only, without chaining.
F
Outline hydraulics diagram (case of chilled water production
F
Thermostat on units
The thermostat THERG controls switching on and off of the different installation units Gn.
THERG is calculated in accordance with the following parameters:
TBAL
ó
Water temperature in the chamber (°C)
CONSEG
ó
Water instruction for regulation of units (°C)
ENCLG
ó
Operating differential for one unit (°C)
DIFETG
ó
Differential between units (°C)
Case of an installation with 4 machines :
ENCLG
DIFETG
THERG
4
3
2
1
0
CONSEG
TBAL
TBAL
Solenoid
valve V2V1
Pump
Buffer
chamber
Evap. G1
unit
Evap. G2
unit
Evap. G3
unit
Evap. Gn
unit