V2.2
-00
47
REMOTE INSTRUCTION UNDETECTED
Logical variable :
DCONS
Incident codes KP02 :
95
KP07 icon :
Description
The unit should be regulated to the water instruction sent remotely by the customer (SGLCONS = 1), but the
signal received is incorrect (TCONS < -25°C).
Action
F
The machine is not stopped and is regulated to its own water instruction.
F
The fault is displayed on the screen.
F
The remote fault report is delayed for 6 minutes.
Resetting
Once TCONS > -25°C, the fault is reset
automatically
.
The machine can once again be regulated to the remote instruction.
Trouble-shooting
Solution
Wiring fault on 4/20mA signal.
Check wiring (see wiring diagram).