Information for the tester
43
4. INFORMATION FOR THE TESTER
4.1 General, Design
Microprocessor-controlled instrument for testing protective measures in electrical
installations and plant as per DIN VDE 0100 and ÖVE-EN1, featuring a 3-digit LCD.
There are eleven available measuring and testing functions:
1)
Protective wire check
IEC/EN 61557-1
2)
Phase connection check
IEC/EN 61557-1
3)
Measurement of voltage
4)
Frequency
5)
Fault current protective circuit check
IEC/EN 61557-6
6)
Earthing/grounding resistance
IEC/EN 61557-5
7)
Insulation resistance
IEC/EN 61557-2
8)
Loop resistance
IEC/EN 61557-3
9)
Earthing/grounding voltage (SEV 3569)
10) Rotary field direction
IEC/EN 61557-7
11) Resistance
IEC/EN 61557-4
In addition to the measured values returned by individual functions, supplementary
measured values can be fetched and stored. Because of this versatility in
measuring facilities, the instrument serves not only for testing purposes but also
supports troubleshooting in electrical plants.
Mode and range selection is effected by a central selector. Four rubber keys are
provided at front panel left for starting measurement, calling complementary
measured values and selecting special modes. This design ensures rapid and
unambiguous single-handed operation.
The measured values are displayed with correct decimal point and with the
appropriate unit on a liquid-crystal display. Various additional special characters
serve to display the measuring mode, the operating status and error conditions.
The instrument has been developed, designed and manufactured in compliance
with the Quality Assurance System DIN ISO 9001.
The auxiliary power source consists of six 1.5 V batteries (IEC R6 or LR6) or six 1.2
V storage batteries of the same size (round cells R6).
The electrical safety complies with IEC/EN61010-1 and the standards‘ series
IEC/EN61557. The housing construction complies with safety class II (
s
) and
protection system IP40.
The instrument is developed manufactured according to the quality assurance
system DIN ISO 9001.
Содержание Saturn 100 Plus
Страница 2: ......
Страница 7: ...Initial power up 5 9 2 1 10 5 4 6 7 8 3 11 A 12...
Страница 13: ...Measuring 11 Flowchart of operation...
Страница 46: ...Information for the tester 44 4 2 Description of Function...
Страница 71: ...Erste Inbetriebnahme 5 9 2 1 10 5 4 6 7 8 3 11 A 12...
Страница 76: ...Messfunktionen 10 Flu diagramm f r Bedienung...
Страница 107: ...Informationen zum Pr fger t 41 4 2 Funktionsbeschreibung...
Страница 126: ...Service 60...
Страница 131: ...Premi re mise en service 5 9 2 1 10 5 4 6 7 8 3 11 A 12...
Страница 138: ...Directives d utilisation 12 Organigramme d utilisation...
Страница 174: ...Informations 48 4 2 Les fonctions...
Страница 199: ...Primo Avvio 6 9 2 1 10 5 4 6 7 8 3 11 A 12...
Страница 204: ...Funzioni di misura 11 Diagramma di flusso per l utilizzo...
Страница 263: ...Puesta en marcha 5 9 2 1 10 5 4 6 7 8 3 11 A 12...
Страница 269: ...Medici n 11...