Voltage – Load “Off” 

 

L1 to L2 – 208 – 250 Volts 

L1 to L3 – 208 – 250 Volts  (Same as 

L1 to L2) L2 to L3 – 0 Volts 

Initial Start Up and Checking Voltage 

 

o

  Turn power on to the static converter.  You may hear a clicking noise from the 

contactor pulling together.  This is normal. 

 

o

  Check Voltage 

 

 

o

 

Start load motor. The red indicator light will turn on and remain illuminated until the Off button is 

pressed. 

 

o

 

If motor runs backwards, switch any two (2) motor leads. 

o

 

Always start machine out of gear or in lowest possible speed/gear. 

o

 

Always start the largest motor when running multiple motors. 

o

 

If motor does not start: 

-

Check (L1-L2) input for correct voltage. 

-

Static Converter may be too small or too large. 

-

Make sure input wire is correct size. 

-

Check load motor for correct wiring. 

 

o

 

If you hear a humming noise coming from the static converter, this is normal. 

 

o

 

Do not start motor more than six (6) times an hour. 

 

 

USE AND CARE 

Unauthorized modification may impair the function and/or safety of this device and could affect the life of the equipment. 

Always check for damaged or worn out parts before using the device. Store it in a secure place out of the reach of 

children when not in use. Inspect for good working condition prior to storage and before re-use. 

REPLACEMENT PARTS 

The MTPC-SCHD series is designed to provide years of reliable performance. Should the need for replacement parts 

arise, please contact Larson Electronics. 

 

 

 

 

 

THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS. 

SHOULD  FURTHER  INFORMATION  NOT  COVERED  BY  THESE  INSTRUCTIONS  BE  REQUIRED,  PLEASE  CONTACT  LARSON  ELECTRONICS  BY  EMAIL  AT 

[email protected] 

OR BY PHONE AT 1-877-348-9680 FOR FURTHER ASSISTANCE. 

PLEASE VISIT LARSONELECTRONICS.COM FOR 

WARRANTY 

AND 

RETURN 

INFORMATION. 

Содержание MTPC-SCHD Series

Страница 1: ...D INSTALLATION MANUAL STATIC PHASE CONVERTERS MTPC SCHD Series WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product Version 1 Created...

Страница 2: ...UIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY...

Страница 3: ...or neutral to T3 Make sure static phase converter and equipment are properly grounded Wire recommendation is based on the use of copper wire If using aluminum wire use the copper equivalent for curren...

Страница 4: ...Phase Converter Idler Motor Wiring and Connection Wiring Method 1 o Single phase power connects through L1 and L2 T3 is the generated phase o Equipment with magnetic controls must operate from L1 and...

Страница 5: ...ing o If you hear a humming noise coming from the static converter this is normal o Do not start motor more than six 6 times an hour USE AND CARE Unauthorized modification may impair the function and...

Страница 6: ...onics com 2019 FORM Static Phase Converter used to start the load motor 1 220V single phase lines L1 and L2 are connected to the A and B terminals of the converter 2 Do not connect 220V power or a gro...

Страница 7: ...phase A static phase converter is used to start the idler motor The idler motor windings act as a rotary transformer or generator and consume little power when running unloaded Used motors are inexpen...

Страница 8: ...Corrective Action 1 Motor will not start A Is your motor single phasing Is your motor turning very slowly and or making a growling or grinding sound a No You do not have single phase power to your ma...

Страница 9: ...er you are using 2 Starting load is too severe for this type of converter Solutions Are a Upgrade your installation to a Rotary Phase Converter b Use a larger approximately 1 3 three phase motor on yo...

Страница 10: ...and provide ample ventilation for the motor 5 Motor may be dirty Check clean motor 6 You may have a bad motor Have motor checked and repaired as required 7 Your motor load may require a higher motor e...

Страница 11: ...onnections are clean and tight 2 You may have used insufficient wire size for the installation 3 You may have used insufficient fuse sizing for the installation You are not running on true three phase...

Отзывы: