TROUBLESHOOTING PROCEDURES 

 

As with any troubleshooting procedure, there is no substitute for a clear understanding of the installation procedures 

involved. The contents of this manual should be studied and THOROUGHLY UNDERSTOOD. 

 

Make 

absolutely certain 

that all factory installation procedures regarding physical mounting, protection from foreign 

material, wire sizing, fuse protection, etc., have been followed. Check all connections to be certain that they are tight. 

 

CAUTION 

- This is a high voltage (220V) device. Disconnect power prior to installing or removing the phase converter or 

attempting to troubleshoot the installation. 

 

 

Problem 

Symptom 

Corrective Action 

 

1. Motor will not start 

 

A.  Is your motor single phasing? 

(Is your motor turning very 

slowly and / or making a 

growling or grinding sound?) 

 

 

a. 

No. 

You do not have 

single phase power to 

your machine. 

 

 

 

b. 

Yes. 

Single phase 

power is reaching your 

machine. Refer to 

Symptom B below. 

 

 

B.  What is the red light doing? 

 

 

a.  Light is flashing on 

and off? 

 

There is a clicking 

sound in the converter. 

 

 

 

 

 

1. You have an open circuit. Check all 

switches, starters, fuses & breakers. 

 

2. Your system is wired incorrectly. 

Make 

absolutely certain 

that M3 (mfg 

leg) is used to power motor only. 

 

 

 

 

 

 

 

 

 

1. Your motor may be wired for 440V. 

Check to determine that the motor is 

wired for 220V. 

 

2. You may have a bad connection. 

Check that all connections are tight. 

 

3. The starting characteristics of your 

motor may not be compatible with this 

phase converter. Some motors have 

special or unique starting 

requirements and a one size smaller 

converter is necessary. 

 

MTPC-SCHD Series 

Содержание MTPC-SCHD Series

Страница 1: ...D INSTALLATION MANUAL STATIC PHASE CONVERTERS MTPC SCHD Series WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product Version 1 Created...

Страница 2: ...UIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY...

Страница 3: ...or neutral to T3 Make sure static phase converter and equipment are properly grounded Wire recommendation is based on the use of copper wire If using aluminum wire use the copper equivalent for curren...

Страница 4: ...Phase Converter Idler Motor Wiring and Connection Wiring Method 1 o Single phase power connects through L1 and L2 T3 is the generated phase o Equipment with magnetic controls must operate from L1 and...

Страница 5: ...ing o If you hear a humming noise coming from the static converter this is normal o Do not start motor more than six 6 times an hour USE AND CARE Unauthorized modification may impair the function and...

Страница 6: ...onics com 2019 FORM Static Phase Converter used to start the load motor 1 220V single phase lines L1 and L2 are connected to the A and B terminals of the converter 2 Do not connect 220V power or a gro...

Страница 7: ...phase A static phase converter is used to start the idler motor The idler motor windings act as a rotary transformer or generator and consume little power when running unloaded Used motors are inexpen...

Страница 8: ...Corrective Action 1 Motor will not start A Is your motor single phasing Is your motor turning very slowly and or making a growling or grinding sound a No You do not have single phase power to your ma...

Страница 9: ...er you are using 2 Starting load is too severe for this type of converter Solutions Are a Upgrade your installation to a Rotary Phase Converter b Use a larger approximately 1 3 three phase motor on yo...

Страница 10: ...and provide ample ventilation for the motor 5 Motor may be dirty Check clean motor 6 You may have a bad motor Have motor checked and repaired as required 7 Your motor load may require a higher motor e...

Страница 11: ...onnections are clean and tight 2 You may have used insufficient wire size for the installation 3 You may have used insufficient fuse sizing for the installation You are not running on true three phase...

Отзывы: