b. Light does not come 

on. 

1. You may have a bad connection or 

an open fuse. Check all fuses and 

connections. 

 

2. You may have the wrong converter. 

Check to see that the motor you are 

attempting to start is within the 

horsepower range of your converter, 

i.e., a converter that is too large for 

your motor will not work. 

2. Motor starts but will not 

come up to full RPM 

A. Motor slows down. Red light 

turns on. Motor RPM increases 

Red light turns off. Unit cycles 

as above. 

1. You may have the wrong size 

converter. Check to see that the motor 

you are attempting to start is within the 

horsepower range of the converter you 

are using. 

 

2. Starting load is too severe for this 

type of converter. 

 

Solutions Are: 

 

a. Upgrade your installation to a 

Rotary Phase Converter. 

 

b. Use a larger (approximately 1 /3) 

three phase motor on your machine. 

3. Motor starts and comes 

up to full RPM but… 

A.  Converter pulsates on/off at 

regular intervals. 

 

 

 

 

 

 

 

 

 

B.  Motor suffers an RPM loss 

under load. 

1. The running load may be too severe 

for this type of converter. Disconnect 

motor drives and if problem is 

eliminated: 

 

a. Upgrade your installation to a 

Rotary Phase Converter. 

 

b. Use a larger (approximately 1/3) 

three phase motor on your machine. 

 

 

1. Your load requires a higher running 

efficiency than your converter is 

allowing. 

 

Solutions Are: 

 

a. Upgrade your installation to a 

Rotary Phase Converter. 

 

b. Install an idler motor into the circuit. 

4. Motor is running 

A.  Improper rotation. 

1. Line leads are hooked up wrong for 

proper rotation. Reverse any two lines 

 

 

 

 

 

Содержание MTPC-SCHD Series

Страница 1: ...D INSTALLATION MANUAL STATIC PHASE CONVERTERS MTPC SCHD Series WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product Version 1 Created...

Страница 2: ...UIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY...

Страница 3: ...or neutral to T3 Make sure static phase converter and equipment are properly grounded Wire recommendation is based on the use of copper wire If using aluminum wire use the copper equivalent for curren...

Страница 4: ...Phase Converter Idler Motor Wiring and Connection Wiring Method 1 o Single phase power connects through L1 and L2 T3 is the generated phase o Equipment with magnetic controls must operate from L1 and...

Страница 5: ...ing o If you hear a humming noise coming from the static converter this is normal o Do not start motor more than six 6 times an hour USE AND CARE Unauthorized modification may impair the function and...

Страница 6: ...onics com 2019 FORM Static Phase Converter used to start the load motor 1 220V single phase lines L1 and L2 are connected to the A and B terminals of the converter 2 Do not connect 220V power or a gro...

Страница 7: ...phase A static phase converter is used to start the idler motor The idler motor windings act as a rotary transformer or generator and consume little power when running unloaded Used motors are inexpen...

Страница 8: ...Corrective Action 1 Motor will not start A Is your motor single phasing Is your motor turning very slowly and or making a growling or grinding sound a No You do not have single phase power to your ma...

Страница 9: ...er you are using 2 Starting load is too severe for this type of converter Solutions Are a Upgrade your installation to a Rotary Phase Converter b Use a larger approximately 1 3 three phase motor on yo...

Страница 10: ...and provide ample ventilation for the motor 5 Motor may be dirty Check clean motor 6 You may have a bad motor Have motor checked and repaired as required 7 Your motor load may require a higher motor e...

Страница 11: ...onnections are clean and tight 2 You may have used insufficient wire size for the installation 3 You may have used insufficient fuse sizing for the installation You are not running on true three phase...

Отзывы: