STATIC PHASE CONVERTER 

INSTRUCTION SHEET

 

 

CAUTION: 

Read the following carefully before 

attempting installation.

 

Using the converter as in Method No. 1  will produce 

approximately 2/3 rated horsepower.

 

Heavily  loaded  applications

,  such  as  compressors, 

blowers,  water  pumps,  hydraulic  pumps,    etc.,    a    50% 

larger  motor  must  be  fitted.  Otherwise,  Method  No.  2, 

shown on reverse side of this page, could be used. Or, use our 

full power Rotary Phase Converter.

 

SELECTION:

 

The horsepower range 

of the static converter is determined by 

the minimum and maximum starting current applied to it at any 

one  time.  The  largest  motor  on  your  machine,  or  the  idler 

motor,  if  used,  must  fall  within  the  minimum  and  maximum 

horsepower  range  marked  on  the  static  converter.  Do  not 

add  the  horsepower  of  the  power  feed,  coolant  pump,  etc. 

These rely on the generator effect  of  the  main  motor.  The 

only  time  you  would  add  the  horsepower  of  two  or  more 

motors  together  would  be if they  always  start  at  exactly  the 

same  time.  Do  not  install  a  larger  size  or  Heavy  Duty 

series  static  converter  thinking  it  will  give  you  more 

horsepower. 

A static converter that is too large will not work 

properly and may cause damage.

 

 

Two-speed  motors 

are  dual  horsepower.  Select  the  static 

phase  converter  with  minimum  and  maximum  horsepower 

ratings,  which  fall  within  or  very  close  to  the  minimum  and 

maximum  horsepower of  the motor.  For example:  A 1.5 HP 

3450 RPM motor is ¾ HP at 1725 RPM.

 

Some European 

soft-start motors draw less starting current 

than normal and therefore require a smaller than normal 

converter. Most Taiwanese and Chinese motors draw greater 

amperage to start than normal. Therefore, for these motors we 

recommend a 3 HP motor; a 5 HP motor; a 7.5 HP motor, etc.

 

WHEN TO USE HEAVY DUTY SERIES

 

Lathes above 3 HP 

not fitted with a clutch.

 

Air  compressors

,  the  motor  pulley  diameter  must  be 

reduced by 1/3, or a 50% larger motor must be fitted.

 

Long,  heavy  starting 

cycles,  frequent  starting  or  instant 

reversing,  unattended  motors,  if  jogging  is  required,  or  if 

there is a chance of the motor being stalled during use.

 

 

 

 

 

 

 

 

Larson Electronics, LLC. 

9419 US-HWY 175 

 

800-369-6671 • FAX 903-498-3364 

www.larsonelectronics.com 

E-mail: [email protected] 

2019 FORM 

 

 

 

 

Static  Phase  Converter  used  to  start  the  load  motor

 

1. 

220V single-phase 

lines L1 and L2 are connected to the A and

 

B terminals of the converter.

 

2. 

Do not connect 

220V power, or a ground or neutral wire from the 

utility, to  the  C terminal  of  the  converter, as the resulting dead 

short would damage it instantly. The single-phase neutral wire is 

not required for operation of the converter.

 

3. 

Properly  ground 

all  electrical  equipment  for  safety.  Use  a 

grounding clip to attach the ground wire to the conduit box.

 

4. 

Fuses 

should not be used on the three-phase lines between the 

static  phase  converter  and  the  motor.  A  blown  fuse  still  leaves 

two lines to conduct, which can damage the converter. Magnetic 

starters  are preferred. Fuses can be used on the single-phase 

lines L1 and L2 from the utility power to the converter. Single- 

phase  wires  and  fuses should  be  sized  as appropriate  for  the 

rated amperage of the motor. See chart below.

 

 

5. 

Size  the  breaker 

on the single-phase approximately twice the 

amperage rating of the motor at the 220V configuration. See chart 

below.

 

6. 

For machines with magnetic switchgear, resistive or  single- 

phase  load: 

Resistive  or  single-phase  loads  and/or  magnetic 

switchgear must be connected only to lines A and C from the 

converter. DO NOT connect the static phase converter until you 

identify which two wires operate the magnetics. To easily locate 

these  two  wires,  connect  220V  single-phase  power  to  any  2  of 

the 3 wires on the machine and press the start button. When the 

correct combination is found the magnetics  will work. Connect 

these  two  wires  to  the  outside  terminals  of  the  converter, 

terminals A and  C, and the  third wire to the center terminal, B. 

The magnetics should still work with the center terminal (line B) 

disconnected. Your motor’s magnetic overload protection remains 

the same; no changes are necessary.

 

 

 

7. 

For indoor use 

only. Do not use in wet or damp locations.

 

8. 

Do not mount 

on equipment with excessive vibrations.

 

9. 

Refer to NEC Code 

#455 for details on field installation issues.

 

 

Breaker & Wire Size - Refer to NEC Code #430 C

 

HP

 

1

 

2

 

3

 

5

 

7.5

 

10

 

15

 

20

 

25

 

30

 

40

 

50

 

Breaker 

Amps

 

15

 

15

 

20

 

30

 

40

 

60

 

100

 

125

 

160

 

200

 

250

 

300

 

Wire Size 

Gauge

 

14

 

14

 

12

 

10

 

8

 

6

 

3

 

1

 

1/O

 

3/O

 

4/O

 

300

 

mcm

 

Fuses*

 

10

 

10

 

15

 

30

 

40

 

45

 

60

 

80

 

100

 

125

 

150

 

200

 

Conduit 

Size In.

 

1/2

 

1/2

 

1/2

 

1/2

 

1/2

 

1/2

 

3/4

 

1

 

1

 

1

-1/4

 

1

-1/4

 

1

-1/2

 

*Fuses

, if used, are 

time delay, dual element 

for 1-phase lines 

L-1 and L-2 only; do not use on 3-phase lines to the motor.

 

Kemp, Tx. 75143 

Содержание MTPC-SCHD Series

Страница 1: ...D INSTALLATION MANUAL STATIC PHASE CONVERTERS MTPC SCHD Series WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product Version 1 Created...

Страница 2: ...UIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY...

Страница 3: ...or neutral to T3 Make sure static phase converter and equipment are properly grounded Wire recommendation is based on the use of copper wire If using aluminum wire use the copper equivalent for curren...

Страница 4: ...Phase Converter Idler Motor Wiring and Connection Wiring Method 1 o Single phase power connects through L1 and L2 T3 is the generated phase o Equipment with magnetic controls must operate from L1 and...

Страница 5: ...ing o If you hear a humming noise coming from the static converter this is normal o Do not start motor more than six 6 times an hour USE AND CARE Unauthorized modification may impair the function and...

Страница 6: ...onics com 2019 FORM Static Phase Converter used to start the load motor 1 220V single phase lines L1 and L2 are connected to the A and B terminals of the converter 2 Do not connect 220V power or a gro...

Страница 7: ...phase A static phase converter is used to start the idler motor The idler motor windings act as a rotary transformer or generator and consume little power when running unloaded Used motors are inexpen...

Страница 8: ...Corrective Action 1 Motor will not start A Is your motor single phasing Is your motor turning very slowly and or making a growling or grinding sound a No You do not have single phase power to your ma...

Страница 9: ...er you are using 2 Starting load is too severe for this type of converter Solutions Are a Upgrade your installation to a Rotary Phase Converter b Use a larger approximately 1 3 three phase motor on yo...

Страница 10: ...and provide ample ventilation for the motor 5 Motor may be dirty Check clean motor 6 You may have a bad motor Have motor checked and repaired as required 7 Your motor load may require a higher motor e...

Страница 11: ...onnections are clean and tight 2 You may have used insufficient wire size for the installation 3 You may have used insufficient fuse sizing for the installation You are not running on true three phase...

Отзывы: