7. Magnetic switch 

chatters or does not 

close. 

A.  Chattering. 

1. You may have a M3 (mfg leg) wired 

to your magnetic coil. M3 (mfg leg) 

must be used to power the motor only. 

8. Excessive blowing of 

fuses, circuit breakers, 

or heaters. 

A.  Instant blowing of fuses or 

circuit breakers. 

 

 

 

B.  Nuisance tripping of fuses, 

circuit breakers, or heaters. 

1. You have a short circuit. Check 

circuit for broken or loose wires. 

Check motor for shorts. Check 

all 

connections. 

 

 

1. 

Y

ou have a bad connection. Check 

that all connections are clean and 

tight. 

 

2. 

Y

ou may have used insufficient wire 

size for the installation. 

 

3. 

Y

ou may have used insufficient fuse 

sizing for the installation. You are not 

running on true three phase; the 

starting & running amperage is often 

higher than it would normally be. To 

solve the problem, go to one step 

higher fuse or breaker or adjust the 

heater to compensate. 

 

4. 

Y

our motor load may require a 

higher motor efficiency than the 

converter is allowing. 

 

Solutions Are: 

 

a. Upgrade your installation to a 

Rotary Phase Converter. 

 

b. Install an idler motor into the circuit. 

 

If at any time you experience a popping sound, see smoke or liquid coming from within the 

converter, you can assume that the converter has internal damage and will have to be returned 

to the factory for repair. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание MTPC-SCHD Series

Страница 1: ...D INSTALLATION MANUAL STATIC PHASE CONVERTERS MTPC SCHD Series WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product Version 1 Created...

Страница 2: ...UIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY...

Страница 3: ...or neutral to T3 Make sure static phase converter and equipment are properly grounded Wire recommendation is based on the use of copper wire If using aluminum wire use the copper equivalent for curren...

Страница 4: ...Phase Converter Idler Motor Wiring and Connection Wiring Method 1 o Single phase power connects through L1 and L2 T3 is the generated phase o Equipment with magnetic controls must operate from L1 and...

Страница 5: ...ing o If you hear a humming noise coming from the static converter this is normal o Do not start motor more than six 6 times an hour USE AND CARE Unauthorized modification may impair the function and...

Страница 6: ...onics com 2019 FORM Static Phase Converter used to start the load motor 1 220V single phase lines L1 and L2 are connected to the A and B terminals of the converter 2 Do not connect 220V power or a gro...

Страница 7: ...phase A static phase converter is used to start the idler motor The idler motor windings act as a rotary transformer or generator and consume little power when running unloaded Used motors are inexpen...

Страница 8: ...Corrective Action 1 Motor will not start A Is your motor single phasing Is your motor turning very slowly and or making a growling or grinding sound a No You do not have single phase power to your ma...

Страница 9: ...er you are using 2 Starting load is too severe for this type of converter Solutions Are a Upgrade your installation to a Rotary Phase Converter b Use a larger approximately 1 3 three phase motor on yo...

Страница 10: ...and provide ample ventilation for the motor 5 Motor may be dirty Check clean motor 6 You may have a bad motor Have motor checked and repaired as required 7 Your motor load may require a higher motor e...

Страница 11: ...onnections are clean and tight 2 You may have used insufficient wire size for the installation 3 You may have used insufficient fuse sizing for the installation You are not running on true three phase...

Отзывы: