STATIC PHASE CONVERTER INSTRUCTION SHEET

 

 

OPERATION

 

For  multiple  motor  applications

,  the  largest  motor  must 

always start first, and it must be at least 50% larger  than  any 

other  motor  starting  on  the  same  converter,  or  if  they  start 

simultaneously  the  combined  horsepower  of  all  the  motors 

must fall within the rating of the converter.

 

Always start a machine 

out of gear or in lowest spindle speed at 

initial hook-up to reduce load. The static converter has a built-in 

weak link, which is designed to fail rapidly if hooked to a higher 

horsepower motor. On lower horsepower motors the light could 

stay on after the motor is running, causing rapid failure of the 

converter,  thus  providing  protection  against  possible  motor  da 

mage.

 

 

The  red  indicator  light 

should  turn on once the motor starts 

and remain on until the OFF button is pressed. When testing the 

static converter for the first few times after  installation,  keep 

your  hand  near  the  off  switch  of  the machine, ready to turn 

it off to prevent  damage  to  the  converter due to a wrong or 

loose connection.

 

Power 

may  be  left  on  the  converter  without  the  load 

applied. Current  draw  is  approximately  8mA  (.008  amp).  The 

converter operates best when mounted vertically. Installation 

should  be  performed  by  a  qualified  electrician.  Refer  to 

local  codes  for proper   wire   sizing.   Wires   and    fuses 

should be  sized  as  appropriate for the motor’s rated 

amperage.

 

 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

 

 

TROUBLESHOOTING

 

 

A. 

If  the  motor  fails  to  start 

and  any  of  the  following 

symptoms  occur: clicking  noises  from  the  static  converter, 

light flashes on and off and motor just hums or buzzes, motor 

starts intermittently; this could indicate that either the motor is 

wired for 460V or  the  static converter being used is too high 

in horsepower for the motor, and a smaller size converter 

should be tried.

 

 

B. 

No voltage 

when measured across lines B and C without 

motor running: Normal indication.

 

C. 

Converter occasionally 

hums  when motor is off: Normal.

 

Static Phase Converter used to start an Idler Motor, Idler Motor 

to power the load motor.

 

Full or close to full horsepower 

(HP) can usually be obtained by 

powering the load motor through a 3-phase motor that runs on 

single-phase. A static phase converter is used to start the idler 

motor.  The  idler  motor  windings  act  as  a  rotary  transformer  or 

generator and consume little power when running unloaded. Used 

motors are inexpensive and readily available. A single machine or 

complete  shop  can  be  operated  with  great  flexibility  using  this 

method. The idler motor should be at least 50% larger than the 

largest motor you want to run to accommodate the higher starting 

current. A good quality 3450 RPM, Y-wound, 3 phase, 220V motor 

is the best choice. A 1725 RPM motor can be used on applications 

not heavily loaded.

 

 

 

1. 

Wire the static phase converter to the idler motor as described 

in Method No. 1, side 1.

 

2. 

Size fuses and wires on the single-phase side as appropriate 

for the motor’s rated amperage. Once running, the idler motor 

can then power the load motor. Wire the load motor in parallel 

to the idler motor as per Method No. 2 diagram below. Size 

fuses and wires on the 3-phase side as appropriate for the 

motor’s rated amperage.

 

3. 

Resistive or single-phase loads and/or magnetic switch gear 

must be energized only by lines A and C from the converter.

 

 

Extra Precautions for Idler Motor System

 

Heavy starting load motor(s) 

may cause the output voltage of the 

idler motor on line B to drop sufficiently to cause the static converter 

to return to the start-up mode. At this point, the converter’s start 

circuit has the combined horsepower of the idler motor and load 

motor(s). This will be indicated by the light on the converter coming 

on when the load motor is started. If the combined  HP is greater 

than  the  converter’s  max.  HP  range,  DAMAGE  TO  THE 

CONVERTER MAY OCCUR.

 

To prevent damage 

to the converter, install a heavy-duty, single- 

pole switch on line B between the static phase converter and the 3- 

pole switch - refer to Method No. 2 diagram below. Switch should be 

rated the same amperage as the idler motor, or greater. The switch 

must  be  in  the  “ON”  (closed)  position  before  the  idler  motor  is 

started, and turned to the “OFF” (open) position after the light on the 

converter  has  gone  out.  This  will  prevent  the  converter  from 

switching  to  the  start-up  mode  and  from  being  damaged  by  an 

overload. Never turn the single-pole switch to the “ON” position while 

the  Idler  Motor  is  running.  Doing  so  could  do  damage  to  the 

converter.

 

 

 

 

Larson Electronics, LLC. 

9419 US-HWY 175 

Kemp, Tx. 75143 

800-369-6671 • FAX 903-498-3364 

www.larsonelectronics.com 

E-mail: [email protected] 

 

 

 

220V 

SINGLE 

PHASE 

Содержание MTPC-SCHD Series

Страница 1: ...D INSTALLATION MANUAL STATIC PHASE CONVERTERS MTPC SCHD Series WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product Version 1 Created...

Страница 2: ...UIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY...

Страница 3: ...or neutral to T3 Make sure static phase converter and equipment are properly grounded Wire recommendation is based on the use of copper wire If using aluminum wire use the copper equivalent for curren...

Страница 4: ...Phase Converter Idler Motor Wiring and Connection Wiring Method 1 o Single phase power connects through L1 and L2 T3 is the generated phase o Equipment with magnetic controls must operate from L1 and...

Страница 5: ...ing o If you hear a humming noise coming from the static converter this is normal o Do not start motor more than six 6 times an hour USE AND CARE Unauthorized modification may impair the function and...

Страница 6: ...onics com 2019 FORM Static Phase Converter used to start the load motor 1 220V single phase lines L1 and L2 are connected to the A and B terminals of the converter 2 Do not connect 220V power or a gro...

Страница 7: ...phase A static phase converter is used to start the idler motor The idler motor windings act as a rotary transformer or generator and consume little power when running unloaded Used motors are inexpen...

Страница 8: ...Corrective Action 1 Motor will not start A Is your motor single phasing Is your motor turning very slowly and or making a growling or grinding sound a No You do not have single phase power to your ma...

Страница 9: ...er you are using 2 Starting load is too severe for this type of converter Solutions Are a Upgrade your installation to a Rotary Phase Converter b Use a larger approximately 1 3 three phase motor on yo...

Страница 10: ...and provide ample ventilation for the motor 5 Motor may be dirty Check clean motor 6 You may have a bad motor Have motor checked and repaired as required 7 Your motor load may require a higher motor e...

Страница 11: ...onnections are clean and tight 2 You may have used insufficient wire size for the installation 3 You may have used insufficient fuse sizing for the installation You are not running on true three phase...