(7.22 continued)
C. Improper or loose wiring.
C. Correct wiring. Refer to wiring
diagram.
D. Starting relay defective.
D. Replace starting relay. Be sure
to use correct relay. Failure to
use correct relay will cause
compressor failure.
E. Defective compressor.
E. Replace compressor.
7.23 Compressor starts and
A. Improper or loose wiring.
A. Correct wiring. Refer to wiring
runs a short time, but
diagram.
shuts off on overload.
B. Low voltage.
B. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
C. Excessively high refrigerant
C. 1. Defective condenser fan
high side pressure and
motor. Replace.
suction return gas hot.
2. Dirty condenser. Clean.
3. Dirty intake air filter. Clean.
4. Back of unit too close to wall.
Move unit away from wall at
least two (2) inches (5.08 cm).
D. Compressor running too hot.
D. Refrigerant leak. Repair and
recharge.
E. Defective compressor.
E. Replace compressor.
19
TROUBLE
CAUSE
REMEDY