7.17 Compressor starts and
A. Faulty ice bank control.
A. Replace ice bank control.
continues to run until
freeze up and will NOT
cut off.
7.18 Warm drinks.
A. Hot incoming water supply
A. Switch to cold water supply.
(from HOT water supply or
heater).
B. No ice bank, defective ice
B. Replace ice bank control.
bank control.
C. Low refrigerant supply.
C. Repair leak and recharge.
D. No ice bank; defective
D. Replace condenser fan motor.
condenser fan motor.
E. No ice bank; compressor
E. Refer to Sections 7.19, 7.20, 7.21,
does not run or runs for a
7.22 and 7.23.
few minutes and stops.
7.19 Compressor does NOT
A. Power supply electrical
A. Reset breaker or replace fuse. If
start (no hum),
breaker tripped or fuse blown.
problem persists:
condenser fan motor
1. Determine reason and correct.
does not run and no
2. Electrical circuit overloaded;
ice bank.
switch to another circuit.
B. Defective ice bank control.
B. Replace ice bank control.
C. Improper or loose wiring.
C. Correct wiring. Refer to wiring
diagram.
D. Low voltage.
D. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
7.20 Compressor does NOT
A. Defective compressor relay
A. Replace compressor relay or
start (no hum), no Ice
or overload.
overload.
bank, but condenser fan B. Defective compressor.
B. Replace compressor.
motor runs.
C. Improper or loose wiring.
C. Correct wiring. Refer to wiring
diagram.
D. Low voltage.
D. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
7.21 Compressor does NOT
A. Improper or loose wiring.
A. Correct wiring. Refer to wiring
start, but hums.
diagram.
B. Low voltage.
B. Measure voltage across common
and run terminal on compressor.
Voltage must not drop below 90%
of rated voltage.
C. Starting relay defective.
C. Replace starting relay. Be sure
to use correct relay. Failure to
use correct relay will cause
compressor failure.
D. Defective compressor.
D. Replace compressor.
7.22 Compressor starts and
A. Low voltage.
A. Measure voltage across common
does switch off of start
and run terminal on compressor.
winding (will only run for
Voltage must not drop below 90%
a few seconds) before
of rated voltage.
internal overload
B. Excessively high refrigerant,
B. This is normal if unit is unplugged
switches compressor
high side pressure.
from electrical outlet then
immediately plugged back into
electrical outlet before refrigerant
pressure has time to equalize.
After about 5 minutes, compressor
will start automatically and run.
(7.22 continued next page)
TROUBLE
CAUSE
REMEDY
18
Содержание CENTURION II 85-0056
Страница 28: ...11 ILLUSTRATIONS PARTS LISTINGS AND WIRING DIAGRAMS 11 1 CENTURION II FINAL ASSEMBLY 24 ...
Страница 30: ...26 11 2 CENTURION II PUMP REGULATOR ASSEMBLY ...
Страница 32: ...11 3 CENTURION II WATER CONCENTRATE COMPONENT ASSEMBLY 28 ...
Страница 34: ...30 11 4 CENTURION II REFRIGERATION ASSEMBLY ...
Страница 38: ...11 7 CENTURION II WIRING DIAGRAM 34 ...