526
Internal comparison: relay output terminal 36 not dropping out.
A19,A7
527
Internal comparison: relay output terminal 41 not dropping out.
A19,A7
528
Internal comparison: relay output terminal 76 not dropping out.
A19,A7
529
Internal comparison: Output K203 not dropping out.
530
Internal comparison: Output K201 entrapping out.
540
ETAMATIC PSU card faulty: optical couplers are not OFF!
541
ETAMATIC PSU card faulty: optical couplers do not come ON!
542
ETAMATIC PSU card: optical couplers or Triac for main gas 1 faulty!
543
ETAMATIC PSU card: optical couplers or Triac for main gas 2 faulty!
544
ETAMATIC PSU card: optical couplers or Triac for oil pump faulty!
545
ETAMATIC PSU card: optical couplers or Triac for oil valve faulty!
546
ETAMATIC PSU card: optical couplers or Triac for ignition transformer faulty!
547
ETAMATIC PSU card: optical couplers or Triac for ignition valve faulty!
550
Oil fuel blocked because a required solenoid valve is not connected.
551
Gas fuel blocked because a required solenoid valve is not connected.
552
No valve connected? Check fuse F3 and F4
600
Program check time of sequencer expired.
H1,H6
601
Leak check fault: gas pressure still applied.
I1,H6,I4
602
Leak check fault: gas pressure missing.
I2,H6,I4
603
Vent gas line manually.
I3
604
Flame signal not arriving in time.
H2
605**
Oil pressure < min. !!!
H5
606*
Gas > min. appears in oil operation.
H3
607*
Ignition position acknowledgement dropping.
H4
608
Boiler safety chain dropping.
609*
Gas safety chain dropping.
610**
Oil safety chain dropping.
611**
Gas pressure too low
612*
Gas pressure too high
613
Air pressure signal missing.
614
F.A safety interl. chain gets OFF
615
Flame is blown away during blow out of oil lance
616
Ignition flame goes out in standby operation
617
Continuous ignition flame goes out under operation
618
Oil circulation: Temperature does not rise up within 45 sec.
620
Oil lance blow out: Delay for opening not kept
621
Oil lance blow out: Oil valve actuator not in ignition position
622
Oil lance blow out: blow out period too long
623
Atomizer switch-ON-pre-period not kept
624
Oil pressure too low
625
Oil pressure too high
626
Atomizer Air pressure too low
Aids FMS
Aids ETA
Содержание FMS Series
Страница 2: ......
Страница 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Страница 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Страница 52: ...51 4 Appendix Oil operation without pilot burner...
Страница 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Страница 62: ...61 4 Appendix To be used only in a grounded power line network FMS 4 FMS 5 with burner firing rate controller...
Страница 73: ......