Voltage supply
230 V + 10% - 15% 50/60 Hz
To be used only in a grounded power line network!
Power input
approx. 34 VA
Ambient temperature
Operation:
+ 0° C…+ 60° C
Transport and
Storage
- 25° C…+ 60° C
Display
Alphanumeric display, 16-digit switchable to set-point, load rating, status, actual value feed-
back, set-point feedback, digital inputs, continuous control output value, correction input
and correction range. Running text display
Admissible ambient
humidity
Class F, DIN 40 040
Inputs and outputs
16 Digital inputs
8 - 16 Digital inputs
1 - 5 Analog outputs
12 Analog outputs
all carrying a potential
Digital signal inputs
16 via floating 24 V DC contact, or optionally via 230 V module, type 6 60 R 0018
The parasitic capacitance of the 2,2 µF line connected to the digital inputs must not be
exceeded by the FMS self-tests. The line length should be limited to 100 m.
Load default
Either potentiometer 1 - 5 k
Ω
current signal (0/4
...
20 mA) or
three-point step control output
Optional: PT 100 direct switching
Feedback inputs
Either potentiometer 1 - 5 k
Ω
current signal (0/4
...
20 mA)
Optional: Namur transmitter direct switching
Control outputs
4 or 5 either continuous or three-point step, on FMS 5 channel 5 fixed continuous.
Resolution
each analog input
999 points, 10 bit
Three-point step
Recommended run-
ning time of servo
drives
30 s…60 s
Содержание FMS Series
Страница 2: ......
Страница 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Страница 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Страница 52: ...51 4 Appendix Oil operation without pilot burner...
Страница 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Страница 62: ...61 4 Appendix To be used only in a grounded power line network FMS 4 FMS 5 with burner firing rate controller...
Страница 73: ......