18
3
System
Operation
Fault Codes
An "H" before the fault code indicates that the main processor has identified the cause of the
defect.
A preceding “Ü” indicates that the monitoring processor has triggered the fault.
An * signifies that re-starting is permitted for this fault.
A blinking Fault-LED means, that a autonomic restart will happen.
** it means, that it tries as many as possible the burner start.
Fault Code Number
Aids FMS
Aids ETA
0
No fault code available for this fault
1
No pilot flame appearing
2
Light/dark check failure
3
Flame fault during ignition
H2
4 **
Flame fault during operation
5
Flame signal does not appear during 1st safety time
H2
6
Flame signal goes out during stabilising time.
H2
7
Flame signal goes out during 1st safety time
H2
8
Flame signal goes out during 2nd safety time
H2
9
Flame signal does not appear during safety time
H2
10
Flame signal goes out immediately after ignition
H2
11
Internal fault: 5 sec. outside light monitoring period not kept
12
Relay module not connected or missing 24V supply for relay
13
Main flame signal appears during ignition
102
Internal fault: Internal communication FIFO has overflowed
A7
103
Internal fault: Error in misc. data
A7,A9
104
Internal fault: D/A converter faulty
A7
105 *
Curve data faulty! Curve set no.:
A7,A13,
A9
106
parameters not equal for parameter no.:
A7,A14,
A9
107
Invalid configuration
A7,A12
108
Different input signals on main processor and monitoring processor.
A7,G8
110
CRC-16 test has found an error
A7,A11
111
RAM test detecting error
A7
112
ETAMATIC self-test exceeds time-out limit
120*
Different operating modes for mon. and main processor
A24
121
Correction is outside permissible range. Channel: 1
F1
122
Correction is outside permissible range. Channel: 2
F1
123
Correction is outside permissible range. Channel: 3
F1
124
Correction is outside permissible range. Channel: 4
F1
125
Correction is outside permissible range. Channel: 5
F1
139
Integr. Flame Detector: self-test fault
140
EEPROM is faulty.
A2, A7,
A12, A15
Содержание FMS Series
Страница 2: ......
Страница 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Страница 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Страница 52: ...51 4 Appendix Oil operation without pilot burner...
Страница 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Страница 62: ...61 4 Appendix To be used only in a grounded power line network FMS 4 FMS 5 with burner firing rate controller...
Страница 73: ......