66
4
Appendix
WARNING!
Using the interface without adapter can damage the unit.
Plug adapter in or remove only with the voltage off.
Only connect units conforming to DIN EN 60950 / VDE 0805.
Number of curve
sets:
2 per channel (e.g. for oil/gas combination burner)
Optional: 4 (2 for oil and 2 for gas)
Pre-setting the oper-
ating condition
By signals from control unit
Memory capacity
Unlimited
Interface
2 serial interfaces on 25-pole Sub-D connector accessible only via adapter
RS 232 (standard setting 19200 baud, parity none, 8 databits, 1 stopbit)
LAMTEC-SYSTEM-BUS
BUS-connection:
Via 25-pole Sub-D connector
BUS card optional for the following systems:
Profibus-DP
Modbus
Ethernet
Interbus-S(Phoenix)
CANopen
Connectable flame
sensor:
Any tested flame sensor with reliable floating contact for flame signalling.
If a flame sensor without approval for continuous operation is connected, the continuous
operation approval for the entire system will lapse.