45
3
System Operation
Re-entering range
limits
TIP:
When adjusting the limit switches after programming, the range limits must be redefined.
TIP:
This may be observed at setpoint switch setting. Without limits, the setpoint value is 0 or 999.
If the limits are defined, the setpoint skips to the actual value.
3.6.2
Installing a New Software Version
Procedure for
installing new
software in the FMS
insert EPROMS
–
M-EPROM on board at the top, left handed
–
main processor-EPROM on board down left handed
Power ON
–
Display: LAMTEC FMS 4/5
–
Self tests
TIP:
Please remember that the installation of modified software in a system that has already un-
dergone acceptance will require a new acceptance or at least approval of the modification by
the competent authorities. The new EPROM numbers (displayed during the start-up self-tests)
are to be inserted accordingly.
Selector switch (2) to "Clear memory”
Press "Enter" (3)
-the curve and the range limits are cleared
Selector switch (2) back to "Automatic"
- "restore previous curve?“ will be displayed
- press Channel Key 3 (5) upwards to quit the message
- "read old curve" will be displayed
- since no point is been entered, the old curve is reactivated,
but the range limits remain clear
Preventilate plant
- Range limits will be reentered.
Содержание FMS Series
Страница 2: ......
Страница 49: ...48 4 Appendix Gas operation without pilot burner with leakage test...
Страница 51: ...50 4 Appendix 4 1 2 Oil Operation Oil operation with pilot burner and flame monitor...
Страница 52: ...51 4 Appendix Oil operation without pilot burner...
Страница 54: ...53 4 Appendix 4 2 Connection Diagram Relay Modules 4 2 1 Connection Diagram Type 660 R 0016...
Страница 62: ...61 4 Appendix To be used only in a grounded power line network FMS 4 FMS 5 with burner firing rate controller...
Страница 73: ......