Design and Functions
4.5.3
Reaction on Gas Deficiency
If main gas 1 valve is open and the pressure drops below the minimum pressure, gas deficien-
cy is detected. This causes a safety shut down and fault indication H611. Further reactions are
depending on the settings in P301 (automatic restart).
If P301 = 1 (no automatic restart) BT300 remains permanently in a fault position and must be
unlocked if gas pressure returns.
If P301 = 0 (automatic restart according to TRD) or P301 = 2 (automatic restart according to
EN676), BT300 waits until the delay in P328 has elapsed and tries to start again then.
If gas deficiency is detected once more the delay will be doubled with every further attempt to
restart until a delay one hour is reached.
The remaining delay is displayed in the User Interface UI300.
Fig. 4-29 Indication of fault H611 gas deficiency with restart
The time until the next start attempt is displayed in the bottom line.
During the waiting time, the red fault lamp on the UI300 lights up permanently. Pressing the
reset button cancels the waiting time and the BT300 immediately makes a new start attempt.
The number of start attempts is unlimited.
4.5.4
Valve Leakage Test Venting Over the Roof
NOTICE
Consider diameter of gas line in the roof purge. For purge, plug X02 is activated for 3 s.
Make sure that this period is sufficient even for smallest purge line diameter!
Содержание BT300 BurnerTronic
Страница 2: ......
Страница 21: ...20 3 Product Description Fig 3 3 UI300 and Fig 3 4 UI300 and dimensional drawings Fig 3 5 UI300 panel cut out...
Страница 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Страница 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Страница 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Страница 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Страница 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Страница 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Страница 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Страница 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Страница 98: ...97 6 Operating Control and Displays...
Страница 99: ...98 6 Operating Control and Displays...
Страница 102: ...101 6 Operating Control and Displays NOTICE If the license agreements are not accepted the installation is aborted...
Страница 103: ...102 6 Operating Control and Displays...
Страница 105: ...104 6 Operating Control and Displays...
Страница 106: ...105 6 Operating Control and Displays...
Страница 107: ...106 6 Operating Control and Displays...
Страница 109: ...108 6 Operating Control and Displays...
Страница 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Страница 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Страница 247: ...243 10 EU Declaration of Conformity...
Страница 248: ...244 10 EU Declaration of Conformity...