168
8
Options
External Firing rate Input
You can establish an external firing rate input if control by atmospheric conditions is activated.
Therefore you must short-circuit terminals 25 and 26. Connect at terminals 16 and 17 a
0/4 ... 20 mA signal for setpoint presetting. Now you can adjust setpoint between a maximum
value at 0/4 mA and a minimum value at 20 mA. If you use setpoint switching, the range of
external setpoint switching is shifted.
External Setpoint Presetting
For the external setpoint values to be activated, parameter 40 must be set to the value 2 (con-
trol by atmospheric condition). The terminals 25, 26 and 27 must be short-circuited. At terminal
16 (-) and 17 (+) of the LCM100, a 0/4 ... 20 mA would be connected.
The following parameter must be set:
Lower limit for mode: ’controlled by atmospheric conditions’ in °C or digit.
This is the lower limit of the outside temperature at mode ’controlled by atmospheric
conditions’.
0 ... 249
0 ... 249 °C / 32 °F ... 480 °F
250 ... 500
-250 ... 0 °C / -418 °F ... 32 °F
475
-25 °C / -13 °F
Example:
Lower limit for mode: setpoint shift in 0,1 mA or digit.
This is the lower limit for the current input in 0,1 mA (min = 0; max = 500)
0 = 0.0 mA
40 = 4.0 mA
200 = 20.0 mA
Group: 20
Min.: 0
Max.: 999
Default:
-25°C
Write: 0/UI
Version: 1.0.0.0
0053
BT300
Firing rate controller: Upper limit [°C] [digit]
Upper limit (for mode: ’controlled by atmospheric conditions’) in 0.1°C or digit.
This is the upper limit of the outside temperature at mode ’controlled by atmospheric
conditions’.
0 ... 249
0.0 ... 24.9 °C/+32 ... 76.82 °F
250 ... 500
-25.0 ... 0.0 °C/-13 ... 32 °F
Upper limit (for mode: Setpoint shift) in 0,1mA. This is the upper limit of the current
input (min = 0, max = 500)
0 = 0.0 mA
40 = 4.0 mA
200 = 20.0 mA
Group: 20
Min.: 0
Max.: 999
Default:
+25°C
Write: 0/UI
Version: 1.0.0.0
Fig. 8-3 External setpoint values
Lower limit
P 52
Upper limit
P 53
Parameter:
0040
2; control by atmospheric condition/setpoint shift
Содержание BT300 BurnerTronic
Страница 2: ......
Страница 21: ...20 3 Product Description Fig 3 3 UI300 and Fig 3 4 UI300 and dimensional drawings Fig 3 5 UI300 panel cut out...
Страница 25: ...24 3 Product Description Fig 3 9 Temperature derating BT300 for operation 2000 m NHN...
Страница 49: ...48 4 Design and Functions Fig 4 20 Oil with pilot burner BT300...
Страница 50: ...49 4 Design and Functions Fig 4 21 Oil without pilot burner BT300...
Страница 51: ...50 4 Design and Functions Fig 4 22 Gas with pilot burner and leakage test BT300...
Страница 52: ...51 4 Design and Functions Fig 4 23 Gas without pilot burner and leakage test BT300...
Страница 53: ...52 4 Design and Functions Fig 4 24 Oil without pilot burner BT335...
Страница 54: ...53 4 Design and Functions Fig 4 25 Gas without pilot burner and leakage test BT335...
Страница 59: ...58 4 Design and Functions Fig 4 28 Leakage test process diagram...
Страница 98: ...97 6 Operating Control and Displays...
Страница 99: ...98 6 Operating Control and Displays...
Страница 102: ...101 6 Operating Control and Displays NOTICE If the license agreements are not accepted the installation is aborted...
Страница 103: ...102 6 Operating Control and Displays...
Страница 105: ...104 6 Operating Control and Displays...
Страница 106: ...105 6 Operating Control and Displays...
Страница 107: ...106 6 Operating Control and Displays...
Страница 109: ...108 6 Operating Control and Displays...
Страница 126: ...125 6 Operating Control and Displays 6 3 4 2 Curve Table Fig 6 37 Curve table window...
Страница 246: ...242 10 EU Declaration of Conformity 10 EU Declaration of Conformity...
Страница 247: ...243 10 EU Declaration of Conformity...
Страница 248: ...244 10 EU Declaration of Conformity...