![Lamborghini Caloreclima FUTURIA 24 MT W TOP Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/lamborghini-caloreclima/futuria-24-mt-w-top/futuria-24-mt-w-top_installation-and-maintenance-manual_3494784013.webp)
56
–
Set the access code (62) (see page 53)
–
Press MODE
–
Press STEP to display the relative PHASE (F-G)
–
Use the +/- keys to set the desired r.p.m.
–
Press STORE to enter the variation.
VARYING FAN R.P.M.
GAS VALVE ADJUSTMENT
The boilers leave the factory already set to their minimum and maximum output and therefore do not need to
be set when installed.
Should the settings need to be modified to adapt them to installation requirements it will be necessary to
change fan r.p.m. and reset the CO
2
value to between 8.8-9%.
Legend
A
Minimum
heat delivery adjustment
screw
B
Maximum
heat delivery
adjustment screw.
In the event of gas valve replacement, proceed as follows:
1
Insert a combustion analysis instrument.
2
Position the switch to SUMMER or WINTER and open a
tap on the hot water circuit.
3
Wait a few seconds for the boiler to reach max. power
(check the fan r.p.m. on the display).
4
Adjust the gas flow-rate by acting on screw B until the
CO
2
value is between 8.8 and 9%.
5
Keep the hot water tap open, select PHASE E and set
parameter “1” to automatically set the boiler to minimum
power.
6
Adjust the gas flow-rate by acting on screw A until the
CO
2
value is between 8.8 and 9%.
7
Repeat steps 4-5-6- until combustion values stabilise
when passing from minimum to maximum power and
vice versa.
When adjustment is over bring PHASE E back from 1 to 0.
This parameter variation restores boiler modulation.
73
CIRCUITO HIDRÁULICO
DESCRIPCIÓN
A
Gas
B
Entrada agua fría
C
Ida acumulador
D
Ida instalación
E
Retorno instalación
F
Retorno acumulador
1
Purgador aire
2
Electrodo de control
3
Acoplamiento inyector
4
Transformador de encendido
5
Electrodos de encendido
6
Sonda de control ida instalación
7
Sonda de control retorno instalación
8
Ventilador
9
Presostato aire
10
Válvula gas
11
Sifón para descarga condensación
12
Vaso de expansión
13
Circulador
14
Preparación para conexión circulador
auxiliar (acumulador)
15
Grifo de llenado
16
Válvula de seguridad
17
Hidrómetro
18
Presostato falta de agua