51
Recommendations
• Use only regeneration salts designed for water softening (EN973).
• For optimal system operation, the use of clean salt, free from impurities, is recommended
(e.g. salt pellets).
• Do not use ice melt salt, block salt, or rock salt.
• The sanitising process (both with liquid and electrochlorination) introduces chlorine
compounds which may reduce the lifetime of the ion exchange resins. Refer to the media
manufacturer specifications sheet for more information.
Manual regeneration
To start manual regeneration:
A
Press and hold
for 5 seconds.
→ The ECO GREEN controller can be used to either start
regeneration immediately or delay it until the programmed
time.
B
Use
and
to scroll between immediate regeneration
(AI) or delayed regeneration (Ad) at the programmed time.
C
Confirm with
.
→ When delayed manual regeneration is chosen, the current day of the week and the
service icon will flash until regeneration starts.
To cancel a regeneration
A
If a regeneration has started, the regeneration can be cancelled by pressing and
holding
for 5 seconds.
→ The controller will then place the valve back in the service position.
Battery operation
Information
During battery operation, regeneration is not carried out
and it is not possible to change the parameters.
Information
If the programmed regeneration mode is volumetric
(delayed or immediate), the time of day and remaining
available volume are displayed alternately.
Caution
The volume is only displayed, not counted down.
Service position search
When powered on, the module may sometimes display F1-| or F2-|, where the number
indicates the first or second attempt to position the controller in service position. A rotating
bar is also shown to indicate that the motor is on. If both searches fail, the message FR01 is
displayed, see 10. Troubleshooting, page 90.