Page 107
1. Boiler display>Configure>Firing rate. Force the fan speed to the desired RPM by navigating through the boiler
display and setting the Fan RPM. Enable fan speed and set the fan speed to desired RPM. Use the following
RPMs to set combustion, 1000, 1500, 2000, 2500, 3000, 3500, 4000, 4500, 5000, and maximum fan speed.
11.E.1 Firing Rate for Boiler
Firing Rate. See Section 8.D.7 on page 72
A Service Video
is available
11.E Combustion setup
The
O
MNI
T
HERM
The OmniTherm uses a sophisticated gas control system that monitors
the gas air ratio and automatically adjusts to maintain proper operating
conditions. On initial installation and subsequent inspections, the CO2 levels
should be checked and if outside the allowable range, adjustments made.
To make adjustments to the gas air ratio use the gas valve display inside the
boiler jacket and follow the process below.