Page 115
Condition
Information
Corrective Action
Stack
Sensor
•
Stack sensor disconnected
•
Stack sensor wiring bad
•
Thermistor elements bad
•
Check the sensor and wiring.
Repair or replace as needed.
•
The stack probe is a dual
element probe with 100K
thermistors. Measure the
resistance of each element
of the sensor and compare
to the resistance table below.
Replace if necessary.
Temp
(°F)
Temp
(°C)
Resistance
(Ω)
32
0
334000
50
10
201660
68
20
125500
77
25
100000
86
30
80220
104
40
52590
122
50
35270
140
60
24160
158
70
16870
176
80
12000
194
90
8674
212
100
6369
248
120
3581
284
140
2117
320
160
1307
356
180
839
392
200
558
428
220
382
464
240
269
500
260
194
536
280
143
Flow Switch
•
Auto reset condition
•
Annunciation – “Flow switch error”
on Message Screen
•
Verify the system is full of water
and all air has been purged from
the system.
•
Verify the boiler/heater is piped
properly into the heating system.
•
Check to see if the pump is on
and rotating in the proper
direction.
•
Confirm all ball valves are open
•
Check wiring to the flow switch
•
Check flow switch operation to
confirm paddle movement and
switch operation.
Lockout: Stack Sensor Probe
Lockout: Stack Sensor Drift