9.D.3 Base Curve Menu
Controls the base A/F ratio curves. These values are set at the factory and can not be adjusted in the field.
9.D.4
Correction Curve Menu
Allows for adjustment of the A/F ratio by the installer. To adjust the A/F curves follow the steps provided.
1.
Set the desired fan speed.
2.
Measure the CO2 with an analyzer.
3.
Start point commissioning.
4. Adjust CO
2 levels. Touch the lean arrows to decrease CO2. Touch Rich arrows to increase CO2. Double
arrows move the CO2 richer or leaner faster than single arrows. In most cases touching the double arrows is
acceptable when adjusting the CO
2.
5.
When the CO2 level is set correctly press set min if setting the min modulation point, press set max if setting
the maximum point, or commission point if setting a point between min and max.
6. Repeat this process until five points have been setup through the modulation range.