Modbus
Address
R/W
Notes
Map Descriptor Name
BACnet
Data
BACnet
Object Read/Write
74
Read
Lag 5 State
AI
74
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
75
Read
Lag 5 Firing Rate
AI
75
Read
Ccrrent firing rate (0-100%)
76
Read
Lag 6 State
AI
76
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
77
Read
Lag 6 Firing Rate
AI
77
Read
Ccrrent firing rate (0-100%)
78
Read
Lag 7 State
AI
78
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
79
Read
Lag 7 Firing Rate
AI
79
Read
Current firing rate (0-100%)
80
Read
Lead 0 State
AI
80
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
81
Read
Lead 0 Firing Rate
AI
81
Read
Current firing rate (0-100%)
82
Read
Lead Firing Rate
AI
82
Read
Current firing rate of the Cascade Lead (0-
100%)
83
Read
Active CH Setpoint
AI
83
Read
0=None
5 = Start
24 = Error Block
160 = Standby
165 = Check Safety Swtich
166 = Run
177 = Prepurge Open
181 = Parameter Block
183 = Lockout
188 = Testmode
194 = Prepurge Closed
195 = Wait for HIS Free
196 = HIS Preheat/Prespark
200 = Verify Primary SF
217 = interpurge
241 = Postpurge
245 = Trial for Ignition
250 = Trial for Ignition Main
52=Post Purge
0 = no CH source
1 = CH1
2 = CH2
5 = External Demand
89
Read
Boiler Pump Status
AI
89
Read
90
Read
Cascade Master Heat Demand
AI
90
Read
91
Read
Burner 1 Run Time
AI
91
Read
i
128
Read/Write CH1 Enable/Disable
AV
0
Read/Write 0 = Disable; 1 = Enable;
129
Read/Write CH1 Set Point
AV
1
Read/Write
130
Read/Write CH1 P
AV
2
Read/Write
131
Read/Write CH1 I
AV
3
Read/Write
132
Read/Write CH1 D
AV
4
Read/Write
133
Read/Write CH2 Enable/Disable
AV
5
Read/Write 0 = Disable; 1 = Enable;
Read
86
Read
84
CH Set Point Source
Burner Status 1
AI
84
Read
AI
86
Read
Modbus
Address
R/W
Notes
Map Descriptor Name
BACnet
Data
BACnet
Object Read/Write
GENERIC LOCKOUT = 17
BURNER1 MAX TRIALS ERROR = 22
BURNER1 MAX FLAME LOST ERROR = 24
BURNER1 FAN SPEED ERROR = 28
NO LOCKOUT = 255
24VDC ERROR = 30
24VAC ERROR = 31
DHW PROBE ERROR = 32
SYSTEM SUPPLY PROBE ERROR = 33
SYSTEM RETURN PROBE ERROR = 34
OUTDOOR PROBE ERROR = 35
FLUE PROBE ERROR = 36
HIGH LIMIT AUTO ERROR = 41
HIGH DELTA T ERROR = 42
FAN SPEED ERROR = 43
38
Read
History - DHW Demand Cycles
AI
38
Read
x 10
39
Read
History - CH1 Demand Cycles
AI
39
Read
x 10
40
Read
History - CH2 Demand Cycles
AI
40
Read
x 10
43
Read
History - Cascade Demand Cycles
AI
43
Read
x 10
44
Read
History - Burner Stage 1 Cycles
AI
44
Read
x 10
48
Read
History - Boiler Pump Cycles
AI
48
Read
x 10
49
Read
History - DHW Pump Cycles
AI
49
Read
x 10
50
Read
History - System Pump Cycles
AI
50
Read
x 10
51
Read
History - Average Boiler Outlet Temperatur
AI
51
Read
°
F
52
Read
History - Maximum Boiler Outlet Temperatu
AI
52
Read
°
F
53
Read
History - Minimum Boiler Outlet Temperatu
AI
53
Read
°
F
54
Read
History - Boiler Average Firing Temperatur
AI
54
Read
°
F
55
Read
History - Boiler Maximum Firing Time
AI
55
Read
Hours
56
Read
History - Boiler Minimum Firing Time
AI
56
Read
Hours
64
Read
Modulation Sensor
AI
64
Read
0 = None
1 = Outlet
2 = DHW
3 = System
4 = Inlet
5 = Flue
6 = System Return
65
Read
Active Service
AI
65
Read
%
66
Read
Lag 1 State
AI
66
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
67
Read
Lag 1 Firing Rate
AI
67
Read
Current firing rate (0-100%)
68
Read
Lag 2 State
AI
68
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
69
Read
Lag 2 Firing Rate
AI
69
Read
Current firing rate (0-100%)
70
Read
Lag 3 State
AI
70
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
71
Read
Lag 3 Firing Rate
AI
71
Read
Current firing rate (0-100%)
72
Read
Lag 4 State
AI
72
Read
0 = Not Present
1 = Not Available
2 = Available
3 = Running
4 = Locked Out
73
Read
Lag 4 Firing Rate
AI
73
Read
Current firing rate (0-100%)
36
Read
Error Code
AI
36
Read
Modbus
Address
R/W
Notes
Map Descriptor Name
BACnet
Data
BACnet
Object Read/Write
134
Read/Write CH2 Set Point
AV
6
Read/Write
135
Read/Write CH2 P
AV
7
Read/Write
136
Read/Write CH2 I
AV
8
Read/Write
137
Read/Write CH2 D
AV
9
Read/Write
148
Read/Write DHW Enable/Disable
AV
20
Read/Write 0 = Disable; 1 = Enable;
149
Read/Write DHW Set Point
AV
21
Read/Write
150
Read/Write DHW P
AV
22
Read/Write
151
Read/Write DHW I
AV
23
Read/Write
152
Read/Write DHW D
AV
24
Read/Write
155
Read/Write Cascade CH Set Point
AV
27
Read/Write
156
Read/Write Cascade CH P
AV
28
Read/Write
157
Read/Write Cascade CH I
AV
29
Read/Write
158
Read/Write Cascade CH D
AV
30
Read/Write
163
Read/Write Hybrid Set Point
AV
35
Read/Write
164
Read/Write Hybrid Differential Temperature
AV
36
Read/Write
165
Read/Write Vari-Prime P - Proportional Term
AV
37
Read/Write
166
Read/Write Vari-Prime I - Integral Term
AV
38
Read/Write
167
Read/Write Vari-Prime D - Derivative Term
AV
39
Read/Write
168
Read/Write Vari-Prime Delta T
AV
40
Read/Write
174
Read/Write DHW Demand switch
BV
0
Read/Write 0 = No Heat Demand; 1 = Heat Demand
175
Read/Write CH 1 Demand switch
BV
1
Read/Write 0 = No Heat Demand; 1 = Heat Demand
176
Read/Write CH 2 Demand switch
BV
2
Read/Write 0 = No Heat Demand; 1 = Heat Demand
179
Read/Write Modbus Parameter Write Enable
The
O
MNI
T
HERM