23
Output
connector
Crimped OT
terminals
M10
10.5mm
26N
•
m
Grounding
connector
Crimped OT
terminals
M10
10.5mm
26N
•
m
500k
Mains input
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Bypass input
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Battery input
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Output
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Grounding
connector
Crimped OT
terminals
M12
14mm
470N
•
m
600k
Mains input
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Bypass input
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Battery input
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Output
connector
Crimped OT
terminals
M16
18mm
120N
•
m
Grounding
connector
Crimped OT
terminals
M12
14mm
470N
•
m
3.6.3
Recommended input front-end and output back-end circuit breakers
UPS capacity
Component
Specifications
150k
Mains input circuit breaker
320A
3P
Bypass input circuit breaker
320A
3P
Output circuit breaker
320A
3P
200k
Mains input circuit breaker
400A
3P
Bypass input circuit breaker
400A
3P
Output circuit breaker
400A
3P
250k
Mains input circuit breaker
500A
3P
Bypass input circuit breaker
500A
3P
Output circuit breaker
500A
3P
300k
Mains input circuit breaker
500A
3P
Bypass input circuit breaker
500A
3P
Output circuit breaker
500A
3P
400k
Mains input circuit breaker
800A
3P
Bypass input circuit breaker
630A
3P
Output circuit breaker
630A
3P
Содержание YMK3300-200k
Страница 1: ...150 600kVA 4256 4774 A...
Страница 10: ...8 200kVA Standard and Full configuration top entry standard configuration full configuration Connect copper bar...
Страница 47: ...45 4 3 4 1 Basic Setting Click basic setting enter by input the correct password The user password is 111111...
Страница 60: ...58 4 3 5 Maint Software update Touch corrention history download and battery self test...
Страница 61: ...59 4 3 5 1 USB Wizard History Outpput download history and setting record by USB 4 3 5 1 1 Alarm Log Output...