71
Storage Temperature
-25
℃~
55
℃
Humidity
0
~
95% non condensing
Altitude <
1500m
Display
Audible & Visual
Line Failure, Battery Low, Overload, System Fault
Status LED
UPS Fault, Alarm and normal
Reading On the LCD
Input Voltage, Input Frequency, Output Voltage, Output
Frequency, Load Percentage, Battery Voltage, parameter
set, history record…
Other
Standard cabinet
Dimensions(W*D*H)
600*850*2000
600*850*2000
1200*850*2000
Full cabinet
Dimensions(W*D*H)
(mm)
1200*850*2000
Module
Dimensions(W*D*H)
(mm)
440*620*130
Cabinet Weight (Kg)
260 280/600 650 720
Module Weight (Kg)
32
Safety Conformance
CE,EN/IEC 62040-3,EN/IEC 62040-1-1
Appendix 2 Problems and Solution
In case the UPS cannot work normally, it might be wrong in installation, wiring or operation.
Please check these aspects first. If all these aspects are checked without any problem, please
consult with local agent right away and provide below information.
(
1
)
Product model name and serial number, which can be found in LCD display.
(
2
)
Try to describe the fault with more details, such as LCD display info, LED lights status, etc.
Read the user manual carefully, it can help a lot for using this UPS in the right way. Some FAQ
(frequently asked questions) may help you to troubleshoot your problem easily.
No.
Problem
Possible reason
Solution
1
LCD not display
The network cable is not
fixed properly or the
telephone line of the front
door is not fixed properly.
Connect the network cable and
telephone cable properly.
2
LCD Blue screen
LCD is Interference
Take out the cable and insert back
properly
3
Utility is connected
but the UPS cannot
be powered ON.
Input power supply is not
connected;
Input voltage low;
The input switch of the
module is not switched on.
Measure if the UPS input
voltage/frequency is within the
window.
Check if all modules input are
switched on
4
Utility normal but
Utility LED does not
light on, and the UPS
operates at battery
mode
The input switch of the
Modules are not switched
on;
input cable is not well
connected
Switch on the input switch;
Make sure the input cable is well
connected.
Содержание YMK3300-200k
Страница 1: ...150 600kVA 4256 4774 A...
Страница 10: ...8 200kVA Standard and Full configuration top entry standard configuration full configuration Connect copper bar...
Страница 47: ...45 4 3 4 1 Basic Setting Click basic setting enter by input the correct password The user password is 111111...
Страница 60: ...58 4 3 5 Maint Software update Touch corrention history download and battery self test...
Страница 61: ...59 4 3 5 1 USB Wizard History Outpput download history and setting record by USB 4 3 5 1 1 Alarm Log Output...