WARNING!
UPON STARTING, PLEASE ENSURE THAT YOU ARE AWARE OF THE LOCATION
AND OPERATION OF THE EXTERNAL ISOLATORS WHICH ARE CONNECTED TO
THE UPS INPUT/BYPASS SUPPLY OF THE MAINS DISTRIBUTION PANEL.CHECK
TO SEE IF THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY
NECESSARY WARNING SIGNS TO PREVENT ANY INADVERTENT OPERATION
3.6.1
Recommended cross-sectional areas for power cables
◆
For future expansion purpose, it is economical to install power cable according to the full rating
capacity initially. The diameter of cable is shown bellow:
UPS
cabinet
Cable Dimension
AC Input
(mm
2
)
BPS Input
(mm
2
)
AC Output
(mm
2
)
DC Input
(mm
2
)
Grounding
(mm
2
)
150
120 120
120
150
50
200
150 150 150 150*2 70
250
95*2 95*2 95*2 120*2 95
300
120*2 120*2 120*2 150*2 120
400
185*2 150*2 150*2
240*2
150
500
150*3 240*2 240*2
185*3
240
600
240*3 150*3 150*3
240*3
240
◆
When selecting, connecting, and routing power cables, follow local safety regulations and rules.
◆
If external conditions such as cable layout or ambient temperatures change, perform
verification in accordance with the IEC-60364-5-52 or local regulations.
◆
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V,
multiply the currents by 0.92.
◆
If primary loads are non-linear loads, increase the cross-sectional areas of neutral
wires1.5–1.7 times.
◆
The nominal battery discharge current refers to the current of forty 12 V batteries at 480V
in standard configuration.
◆
The maximum battery discharge current refers to the current when forty 12 V batteries in
standard configuration, that is, two hundred and forty 2 V battery cells (1.67 V/cell), stop
discharging.
◆
The battery cable specifications are selected based on 40 batteries by default and
compatible with application scenarios with 30–50 batteries.
◆
When the mains input and bypass input share a power source, configure both types of input
power cables as mains input power cables. The cables listed in Table are used only when
the following requirements are met:
−
Routing mode: Routing the cables over the cable ladder or bracket in a single layer
(IEC60364-5-52 middle E).
−
The ambient temperature is 30°C.
−
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
−
90°C copper flexible cable.
−
The length of the AC power cables of a UPS is no longer than 30 m and DC power cables
no longer than 50 m.
Содержание YMK3300-200k
Страница 1: ...150 600kVA 4256 4774 A...
Страница 10: ...8 200kVA Standard and Full configuration top entry standard configuration full configuration Connect copper bar...
Страница 47: ...45 4 3 4 1 Basic Setting Click basic setting enter by input the correct password The user password is 111111...
Страница 60: ...58 4 3 5 Maint Software update Touch corrention history download and battery self test...
Страница 61: ...59 4 3 5 1 USB Wizard History Outpput download history and setting record by USB 4 3 5 1 1 Alarm Log Output...