EOD Battery Volt:
End of discharge voltage. The value can be 1.60~1.90, and is 1.80 by
default.
Float Temp Compen Coeff:
modify the voltage of compensation after enable theswtich.
the value can be 0.001~0.007/cell, and is 0.003 by default.
Boost Charge Setting:
Boost charge disable or enable, and is enable by default.
No Battery Warning:
can be no warning when no batter after set disable, and is enable
by default.
Bypass Volt Prot Lower Limit:
When the difference between the bypass voltage and
the rated voltage exceeds the lower threshold for the bypass voltage, the system
determines that the bypass voltage is abnormal and that the bypass is unavailable. The
value can be –10%, –15%, –20%, –30%, –45%,. The default value is –45%.
Bypass Volt Prot Limit:
When the difference between the bypass voltage and the rated
voltage exceeds the upper threshold for the bypass voltage, the system determines that
the bypass voltage is not normal and that the bypass is unavailable.