NOTE:
When the voltage level is 380 V, the value range is 10%, 15%, 20%, and 25% (default).
When the voltage level is 400 V, the value range is 10%, 15%, and 20% (default).
When the voltage level is 415 V, the value range is 10% and 15%(default).
Bypass Freq Tracking Range:
When the difference between the bypass input
frequency and the ratedfrequency is greater than this value, the system determines
that the bypass frequency is not normal, and that the bypass is unavailable. The
value range is 1%, 2%, 4%, 5%, 10%(default).
Bypass rate tracking rate:
Inverter frequency tracking to bypass frequency rate.The
value range is 0.5~2, and is 1 by default.
Bypass Over Temp Power Supply:
Specifies whether to start bypass mode when
overtemperature occurs. The default value is Enable.
Bypass Swtiches Limit:
Cross currents occur during the transfer between bypass mode
and normal mode, which impacts the system. This parameter specifies the number of
transfers between bypass mode and normal mode within 1 hour, which ensures
system security. The value can be 3 to 10, and is 10 by default.