Parameter
Description
Factory setting
Setting range/options
Access
3-7-1-4
Function of digital input 4
9
See selection list
Customer
3-7-1-5
Function of digital input 5
2
See selection list
Customer
Table 24: Selection list for parameters
Selection list for parameters
3-7-1-2 to 3-7-1-5
Description
1 – No function
No function
2 – Reset
Reset after alert;
CAUTION: possible restart
3 – System Start
System start for multiple pump system
4 – Start
Pump start in automatic mode
5 – Ramp Select
Selection of ramp 1 or 2
6 – No function
No function
7 – Pset OutF Bit 0
Bit 0 for digital selection of fixed speed
8 – Pset OutF Bit 1
Bit 1 for digital selection of fixed speed
9 – Preset Setpt +
Setpoint increase via digital pulses
10 – Preset Setpt -
Setpoint decrease via digital pulses
11 – No function
No function
12 – Pset AOUT Bit 0
Bit 0 for selecting the output variable on the analog output
13 – Pset AOUT Bit 1
Bit 1 for selecting the output variable on the analog output
8.7.5 Relay output
Operating status information can be queried on the two volt-free contacts (NO relay)
of the PumpDrive:
Parameter
Description
Factory setting
Setting range/options Access
3-7-2-1
Function of digital output 1
29
See selection list
Customer
3-7-2-2
Time delay between event and
response (On time delay)
1
0..360 [s]
Customer
3-7-2-3
Time delay between event and
response (Off time delay)
1
0..360 [s]
Customer
3-7-3-1
Function of digital output 2
4
See selection list
Customer
3-7-3-2
Time delay between event and
response (On time delay)
1
0..360 [s]
Customer
3-7-3-3
Time delay between event and
response (Off time delay)
1
0..360 [s]
Customer
Selection list for parameters 3-7-2-1 and 3-7-3-1
1 – No function
12 – Low Current
24 – Low An IN2
2 – PDrive Ready
1 – Frequency Range
25 – Thermal Warn
3 – Enable/No Warn
14 – High Frequency
26 – Rdy/No Temp Wrn
4 – Running
15 – Low Frequency
27 – Rdy/No Line Wrn
5 – Running/No Warn
16 - Power Range
28 – Rdy/V Range OK
6 – Setpt/No Warn
17 – High Power
29 – No Alert
7 – Alert
18 – Low Power
30 – Drive MAN Mode
8 – Alert or Wrn
19 – An IN1 Range
31 – Drive MAN Mode
9 – At Current Lim (i
2
t)
20 – High An IN1
32 – Setpoint OK
10 – Current Range
21 – Low An IN1
33 – Feedback OK
11 – High Current
22 – An IN2 Range
34 – Sleep, Stand-By
23 – High An IN2
35 – ON>maxP,OFF<min
8 Operating the Pressure Booster System
40 of 56