8.6.1 Parameter group 1 "Operation"
Access via "Operation" key
Parameters starting with the digit "1" indicate current operating conditions.
Exception: parameters 1-1-1-5 and 1-1-1-6, which can be used to reset the kWh and
operating hours counters.
Parameter
Description
1-1-1-2
Operating hours counter [h]
1-3-1-1
Feedback/actual value [bar]
1-3-1-3
Setpoint [bar]
8.6.2 Parameter group 2 "Diagnosis"
Access via "Diagnosis" key
Parameters starting with the digit "2" are used for fault diagnosis. (
Parameter
Description
2-1-1
Alert history, list of alerts which can be acknowledged individually by pressing OK
2-2-1
Warnings
2-3-1
Alerts
8.6.3 Parameter group 3 "Settings"
Access via "Settings" key
This key is used to change parameters which are required to adjust the pressure
booster system to site conditions if the data specified in the purchase order no longer
applies or if accessories or supplementary equipment have been retrofitted.
Parameter
Description
3-1-4-1
[Man] key: Disable or enable key for manual operation.
3-1-4-2
[Off] key: Disable or enable key for switching off the system.
3-1-6
Password: Log on with the required access level.
3-4-3
Sleep mode: Settings for stopping the pump at Q = 0 (
3-5-2-1
Preset setpoint: Setting the setpoint
3-9-1-2
PI Prop Gain: Changing the proportional gain of the PI controller
3-9-1-3
PI Integral TM: Changing the integral term of the PI controller
8.6.4 Parameter group 4 "Information"
Access via "Information" key
Parameters starting with the digit "4" provide information on:
Parameter
Description
4-1
PumpDrive
4-2
Panel
8.7
Adjusting the settings
8.7.1 Setting the setpoint
The pressure booster system is factory-set to the setpoint indicated on the rating
plate.
If the setpoint needs to be adjusted to site conditions, parameter 3-5-2-1 has to be
changed as required.
Fig. 10: Operation key
Fig. 11: Diagnosis key
Fig. 12: Settings key
Fig. 13: Information key
8 Operating the Pressure Booster System
36 of 56